Levelflex FMP50 PROFIBUS PA Important document information Important document information Purpose of this document These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Important document information Levelflex FMP50 PROFIBUS PA Flat blade screwdriver Torx screwdriver Allen key Open-ended wrench 1.2.4 Symbols for certain types of information and graphics Permitted Procedures, processes or actions that are permitted Preferred Procedures, processes or actions that are preferred Forbidden...
For an overview of the scope of the associated Technical Documentation, refer to the following: • Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix code on nameplate. 1.3.1 Technical Information (TI)
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple®...
The manufacturer is not liable for damage caused by improper or non-intended use. Clarification of borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
Basic safety instructions Levelflex FMP50 PROFIBUS PA Workplace safety When working on and with the device: ‣ Wear the required protective equipment according to federal or national regulations. Operational safety Risk of injury! ‣ Operate the device only if it is in proper technical condition, free from errors and faults.
• Do the nameplate data match the ordering information on the delivery note? • If required (see nameplate): are the Safety Instructions (XA) provided? If one of these conditions is not met, please contact your Endress+Hauser sales office. Product identification The following options are available for the identification of the measuring device: •...
Levelflex FMP50 PROFIBUS PA Storage, transport Storage, transport Storage temperature • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F) • Use original packaging. Transporting the product to the measuring point WARNING Housing or rod may become damaged or pull off.
Mounting Levelflex FMP50 PROFIBUS PA Mounting Mounting requirements 6.1.1 Suitable mounting position A0012606 4 Installation conditions for Levelflex Spacing requirements when mounting • Distance (A) between the vessel wall and rod and rope probes: • For smooth metallic walls: > 50 mm (2 in) •...
Page 17
Levelflex FMP50 PROFIBUS PA Mounting Additional conditions • When mounting outdoors, a weather protection cover (1) can be used to protect the device against extreme weather conditions. • In metallic vessels, preferably do not mount the probe in the center of the vessel (2), as this would lead to increased interference echoes.
Mounting Levelflex FMP50 PROFIBUS PA 6.1.2 Mounting under confined conditions Mounting with remote probe The device version with a remote probe is suitable for applications with restricted mounting space. In this case, the electronics housing is mounted at a separate position from the probe.
Levelflex FMP50 PROFIBUS PA Mounting 6.1.3 Notes on the mechanical load of the probe Tensile loading capacity of rope probes FMP50 Rope 4mm (1/6") 316 2 kN Lateral loading capacity (flexural strength) of rod probes FMP50 Rod 8mm (1/3") 316L...
Page 20
Mounting Levelflex FMP50 PROFIBUS PA Bending torque [M] on rod probes, diameter 8mm (1/3”) 20.0 18.0 16.0 14.0 12.0 10.0 v=0.5m/s v=0.7m/s v=1.0m/s Probe length [ ] in meters A0014182-EN Endress+Hauser...
Levelflex FMP50 PROFIBUS PA Mounting 6.1.4 Information concerning the process connection Probes are mounted on the process connection with threaded connections or flanges. If there is the danger with this installation that the probe end moves so much that it occasionally touches the vessel floor or cone, the probe may need to be shortened at the lower end and fixed in place.
Page 22
Mounting Levelflex FMP50 PROFIBUS PA Mounting in nozzles ≥ DN300 If installation in nozzles ≥ 300 mm (12 in) is unavoidable, installation must be carried out in accordance with the following diagram in order to avoid interference signals in the near range.
Levelflex FMP50 PROFIBUS PA Mounting 6.1.5 Securing the probe Securing rope probes A0012609 Rope sag: ≥ 10 mm/(1 m probe length) [0.12 in/(1 ft probe length)] Reliably grounded end of probe Reliably insulated end of probe Fastener in female thread of probe end weight Insulated fastening kit •...
Page 24
Mounting Levelflex FMP50 PROFIBUS PA Securing rod probes • For WHG approval: A support is required for probe lengths ≥ 3 m (10 ft). • In general, rod probes must be secured in the event of horizontal flow (e.g. from an agitator) or strong vibrations.
Levelflex FMP50 PROFIBUS PA Mounting 6.1.6 Special installation situations Bypasses and stilling wells The use of centering disks/stars/weights (available as accessories) is recommended in bypass and stilling well applications. As the measuring signal penetrates many plastics, installation in plastic bypasses or stilling wells can produce incorrect results.
Page 26
Mounting Levelflex FMP50 PROFIBUS PA Underground tanks A0014142 In the case of nozzles with large diameters, use FMP51 with a coax probe to avoid reflections at the nozzle wall. Endress+Hauser...
Page 27
Levelflex FMP50 PROFIBUS PA Mounting Mounting at an angle A0014145 • For mechanical reasons, the probe should be installed as vertically as possible. • If the probe is installed at an angle, the length of the probe must be reduced depending on the angle of installation.
Page 28
Mounting Levelflex FMP50 PROFIBUS PA Non-metal vessels A0012527 Non-metal vessel Metal sheet or metal flange To ensure good measurement results when mounting on non-metal vessels, at the process connection mount a metal sheet with a diameter of at least 200 mm (8 in) at a right angle to the probe.
Page 29
Levelflex FMP50 PROFIBUS PA Mounting Plastic and glass vessels: Mounting the probe on the outside wall In the case of plastic and glass vessels, the probe can also be mounted on the outside wall under certain conditions. A0014150 Plastic or glass vessel...
Page 30
Mounting Levelflex FMP50 PROFIBUS PA 2. Parameter Expert → Sensor → Gas phase compensation → Const. GPC factor Quotient: Enter "(actual probe length)/(measured probe length)". Compensation via the calibration parameters If it is necessary to actually compensate for a gas phase, the gas phase compensation function is not available for the correction of external mounting.
Page 31
Levelflex FMP50 PROFIBUS PA Mounting Vessel with thermal insulation If process temperatures are high, the device must be included in normal vessel insulation (1) in order to prevent the electronics heating up as a result of thermal radiation or convection. The insulation may not go beyond the points labeled "MAX" in the drawings.
Mounting Levelflex FMP50 PROFIBUS PA Mounting the measuring device 6.2.1 Tool list AF 8 mm AF 36 mm 3 mm 6 mm 4 mm • To shorten rope probes: use a saw or bolt cutters • To shorten rod or coax probes: use a saw •...
Levelflex FMP50 PROFIBUS PA Mounting 3. Measure off the new rope length. 4. At the point to be shortened, wrap adhesive tape around the rope to prevent it from fraying. 5. Saw off the rope at a right angle or cut it off with a bolt cutter.
Mounting Levelflex FMP50 PROFIBUS PA Screw the device with the threaded connection into a sleeve or flange and then secure it to the process vessel via the sleeve/flange. • When screwing into place, turn by the hex bolt only: • Thread 3/4": 36 mm •...
Page 35
Levelflex FMP50 PROFIBUS PA Mounting CAUTION Mechanical stress can damage the plugs of the connection cable or cause them to become loose. ‣ Mount the probe and the electronics housing securely before connecting the connecting cable. ‣ Lay the connecting cable in such a way that it is not exposed to mechanical stress.
Levelflex FMP50 PROFIBUS PA Mounting 6.2.6 Turning the display Opening the cover 3 mm A0021430 1. Loosen the screw of the securing clamp of the electronics compartment cover using an Allen key (3 mm) and turn the clamp 90 ° counterclockwise.
Page 38
Mounting Levelflex FMP50 PROFIBUS PA Does the device comply with the measuring point specifications? • Process temperature • Process pressure • Ambient temperature range • Measuring range Are the measuring point identification and labeling correct (visual inspection)? Is the device adequately protected against precipitation and direct sunlight? Is the device adequately protected against impact?
Levelflex FMP50 PROFIBUS PA Electrical connection Electrical connection Connecting requirements 7.1.1 Terminal assignment Terminal assignment, 4-wire: 4 to 20 mA HART (90 to 253 V A0036519 9 Terminal assignment, 4-wire: 4 to 20 mAHART (90 to 253 V Connection 4 to 20 mA HART (active): terminals 3 and 4...
Page 40
Electrical connection Levelflex FMP50 PROFIBUS PA Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus A0036500 10 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus Without integrated overvoltage protection With integrated overvoltage protection Connection, PROFIBUS PA / FOUNDATION Fieldbus: terminals 1 and 2, without integrated overvoltage...
Levelflex FMP50 PROFIBUS PA Electrical connection Connection examples for the switch output A0015909 12 Connection of a relay A0015910 13 Connection to a digital input Pull-up resistor Digital input For optimum interference immunity we recommend to connect an external resistor (internal resistance of the relay or pull-up resistor) of <...
< 1.5 pF Nominal arrest impulse voltage (8/20 μs) 10 kA External overvoltage protection module HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection. For detailed information please refer to the following documents: • HAW562: TI01012K • HAW569: TI01013K...
Levelflex FMP50 PROFIBUS PA Electrical connection Connecting the device WARNING Explosion Hazard! ‣ Observe applicable national standards. ‣ Comply with the specifications in the Safety Instructions (XA). ‣ Use specified cable glands only. ‣ Check to ensure that the power supply matches the information on the nameplate.
Electrical connection Levelflex FMP50 PROFIBUS PA 5. Connect the cable according to the terminal assignment. A0034682 6. If using shielded cables: Connect the cable shield to the ground terminal. 7.2.3 Plug-in spring-force terminals The electrical connection of device versions without an integrated overvoltage protection is via plug-in spring-force terminals.
Page 45
Levelflex FMP50 PROFIBUS PA Electrical connection Do the mounted cables have adequate strain relief? Are all the cable glands installed, firmly tightened and leak-tight? Does the supply voltage match the specifications on the nameplate? Is the terminal assignment correct? If necessary, has a protective ground connection been established?
Operation methods Levelflex FMP50 PROFIBUS PA Operation methods Overview 8.1.1 Local operation Operation Pushbuttons Touch Control with Order code for Option C "SD02" Option E "SD03" "Display; Operation" A0036312 A0036313 Display 4-line display 4-line display elements white background lighting; switches to red in...
Computer with PROFIusb and operating tool (e.g. DeviceCare/FieldCare ) PLC (programmable logic controller) Transmitter Additional functions (valves etc.) Via service interface (CDI) A0039148 Computer with FieldCare/DeviceCare operating tool Commubox FXA291 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface) Endress+Hauser...
Operation methods Levelflex FMP50 PROFIBUS PA Structure and function of the operating menu 8.2.1 Structure of the operating menu Menu Submenu / Meaning parameter Language Defines the operating language of the local display Commissioning Launches the interactive wizard for guided commissioning.
Page 49
Levelflex FMP50 PROFIBUS PA Operation methods Menu Submenu / Meaning parameter Communication Contains all parameters needed to configure the digital communication interface. Diagnostics Contains all parameters needed to detect and analyze operational errors. If you are operating via operating tools (e.g. FieldCare), the "Language" parameter is located under "Setup ...
Operation methods Levelflex FMP50 PROFIBUS PA 8.2.2 User roles and related access authorization The two user roles Operator and Maintenance have different write access to the parameters if a device-specific access code has been defined. This protects the device configuration via the local display from unauthorized access (Verweisziel existiert nicht, aber @y.link.required=' t rue' )
Page 51
Levelflex FMP50 PROFIBUS PA Operation methods Disabling write protection via access code If the symbol appears in front of a parameter on the local display, the parameter is write-protected by a device-specific access code and its value cannot currently be changed via the local display →...
Page 52
Operation methods Levelflex FMP50 PROFIBUS PA XXXXXXXXXXXXX 3 mm A0026157 1. Loosen the securing clamp. 2. Unscrew the electronics compartment cover. 3. Pull out the display module with a gentle rotational movement. To make it easier to access the write protection switch, attach the display module to the edge of the electronics compartment.
Page 53
Levelflex FMP50 PROFIBUS PA Operation methods 4. Setting the write protection switch (WP) on the main electronics module to the ON position enables hardware write protection. Setting the write protection switch (WP) on the main electronics module to the OFF position (factory setting) disables hardware write protection.
Page 54
Operation methods Levelflex FMP50 PROFIBUS PA Enabling and disabling the keypad lock Access to the entire operating menu via local operation can be locked via the keypad lock. When access is locked, it is no longer possible to navigate through the operating menu or change the values of individual parameters.
Levelflex FMP50 PROFIBUS PA Operation methods Display and operating module 8.3.1 Display User ABC_ DEFG HIJK LMNO PQRS TUVW A0012635 18 Display format on the display and operating module Measured value display (1 value max. size) 1.1 Header containing tag and error symbol (if an error is active) 1.2 Measured value symbols...
Page 56
Operation methods Levelflex FMP50 PROFIBUS PA Display symbols for the submenus Symbol Meaning Display/operat. Is displayed: • In the main menu next to the "Display/operat." selection A0018367 • In the header on the left in the "Display/operat." menu Setup Is displayed: •...
Page 57
Levelflex FMP50 PROFIBUS PA Operation methods Measured value symbols Symbol Meaning Measured values Level A0032892 Distance A0032893 Current output A0032908 Measured current A0032894 Terminal voltage A0032895 Electronics or sensor temperature A0032896 Measuring channels Measuring channel 1 A0032897 Measuring channel 2...
Operation methods Levelflex FMP50 PROFIBUS PA 8.3.2 Operating elements Meaning Minus key In a menu, submenu Moves the selection bar upwards in a picklist. A0018330 In the text and numeric editor In the input mask, moves the selection bar to the left (backwards).
Levelflex FMP50 PROFIBUS PA Operation methods 8.3.3 Entering numbers and text Numeric editor Text editor User ABC_ DEFG HIJK LMNO PQRS TUVW A0013999 A0013941 Editing view Display area of the entered values Input mask Operating elements Input mask The following input and operating symbols are available in the input mask of the numeric...
Operation methods Levelflex FMP50 PROFIBUS PA Toggle • Between upper-case and lower-case letters • For entering numbers A0013981 • For entering special characters Confirms selection. A0013985 Switches to the selection of the correction tools. A0013987 Exits the input without applying the changes.
Page 61
Levelflex FMP50 PROFIBUS PA Operation methods 3. Press to confirm the selection. The selected menu opens. Endress+Hauser...
Integration into a PROFIBUS network Levelflex FMP50 PROFIBUS PA 8.3.5 Envelope curve display on the display and operating module In order to assess the measuring signal, the envelope curve and - if a mapping has been recorded - the mapping curve can be shown on the display and operating module:...
Levelflex FMP50 PROFIBUS PA Integration into a PROFIBUS network Setting the device address A0015686 19 Address switch in the connection compartment 9.2.1 Hardware addressing 1. Set switch 8 to the "OFF" position. 2. Using switches 1 to 7, set the address as indicated in the table below.
Commissioning using the Commissioning Wizard Levelflex FMP50 PROFIBUS PA Commissioning using the Commissioning Wizard A Wizard is provided in FieldCare and DeviceCare that guides the user through the initial commissioning process. 1. Connect the device with FieldCare or DeviceCare. 2. Open the device in FieldCare or DeviceCare.
Levelflex FMP50 PROFIBUS PA Commissioning via operating menu Commissioning via operating menu 11.1 Function check Before commissioning your measuring point, ensure that the post-installation and post- connection checks have been performed: 11.2 Setting the operating language Factory setting: English or ordered local language X X X X X X X 20.50...
Commissioning via operating menu Levelflex FMP50 PROFIBUS PA 11.3 Configuring level measurement 20 mA 100% 4 mA A0011360 23 Configuration parameters for level measurement in liquids Probe length Reference point of measurement Distance Level Empty calibration (= zero point) Full calibration (= span) If the ε...
Page 67
Levelflex FMP50 PROFIBUS PA Commissioning via operating menu 11. Navigate to: Setup → Signal quality Displays the signal quality of the analyzed level echo. 12. Operation via local display: Navigate to: Setup → Mapping → Confirm distance Compare the distance displayed with the actual value to start recording an interference echo map (where applicable).
Commissioning via operating menu Levelflex FMP50 PROFIBUS PA 11.4 Recording the reference envelope curve After the measurement has been configured, it is recommended to record the current envelope curve as a reference envelope curve. This can then be used later for diagnostic purposes.
Levelflex FMP50 PROFIBUS PA Commissioning via operating menu 11.5 Configuring the local display 11.5.1 Factory setting of local display for level measurements Parameter Factory setting for devices with 1 current Factory setting for devices with 2 current output outputs Format display 1 value, max. size 1 value, max.
Commissioning via operating menu Levelflex FMP50 PROFIBUS PA 11.6 Configuration management After commissioning, you can save the current device configuration, copy it to another measuring point or restore the previous device configuration. You can do so using the Configuration management parameter and the options available.
Levelflex FMP50 PROFIBUS PA Commissioning via operating menu 11.7 Protecting settings from unauthorized access The settings can be protected from unauthorized access in two ways: • Locking via parameters (software locking) • Locking via write protection switch (hardware locking) Endress+Hauser...
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting 12.1 General troubleshooting 12.1.1 General errors Error Possible cause Solution Device does not respond. Supply voltage not connected. Connect the correct voltage. The cables do not contact the Ensure electrical contact between terminals properly.
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting 12.1.2 Parametrization errors Parametrization errors for level measurements Problem Possible cause Remedy Measured value is incorrect If measured distance (Setup • Check the Empty calibration → Distance) matches the real parameter (→ 110) and correct if distance: necessary.
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA 12.2 Diagnostic information on local display 12.2.1 Diagnostic message Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the measured value display. Measured value display in alarm condition...
Page 75
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting Diagnostic event and event text The fault can be identified by means of the diagnostic event. The event text helps you by providing information about the fault. In addition, the associated status symbol is displayed in front of the diagnostic event.
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA 12.2.2 Calling up remedial measures X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2...
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting 12.3 Diagnostic event in the operating tool If a diagnostic event is present in the device, the status signal appears in the top left status in the operating tool along with the corresponding symbol for event level in accordance with NAMUR NE 107: •...
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA 3. Click "Save as ..." and save a PDF of the protocol. The protocol contains the diagnostic messages and remedy information. C: Via the "Eventlist / Extended HistoROM" function Select the "Eventlist / Extended HistoROM" function.
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting 12.5 List of diagnostic events Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic of sensor Broken probe detected 1. Check map Alarm 2. Check sensor...
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Linearization Check linearization table Alarm Configuration 1. Restart device Alarm incompatible 2. Contact service Dataset 1. Check data set file Warning 2.
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting Navigation path Diagnostics → Event logbook → Event list A maximum of 100 event messages can be displayed in chronological order. Die Ereignishistorie umfasst Einträge zu: • Diagnostic events • Information events In addition to the operation time of its occurrence, each event is also assigned a symbol that indicates whether the event has occurred or is ended: •...
Page 82
Diagnostics and troubleshooting Levelflex FMP50 PROFIBUS PA Info number Info name I1185 Display backup done I1186 Restore via display done I1187 Settings downloaded with display I1188 Display data cleared I1189 Backup compared I1256 Display: access status changed I1264 Safety sequence aborted...
Levelflex FMP50 PROFIBUS PA Diagnostics and troubleshooting 12.7 Firmware history Date Firmware Modifications Documentation (FMP50, PROFIBUS) version Operating Instructions Description of Device Technical Information Parameters 07.2011 01.00.zz Original software BA01005F/00/EN/10.10 GP01001F/00/EN/10.10 TI01000F/00/EN/13.11 02.2015 01.01.zz • Support of SD03 BA01005F/00/EN/14.14 GP01001F/00/EN/13.14 TI01000F/00/EN/17.14...
Maintenance Levelflex FMP50 PROFIBUS PA Maintenance No special maintenance work is required. 13.1 Exterior cleaning When cleaning the exterior, always use cleaning agents that do not corrode the surface of the housing and the seals. 13.2 General cleaning instructions Dirt or buildup may form on the probe depending on the application. A thin, even layer has little impact on the measurement.
General information 14.1.1 Repair concept Under the Endress+Hauser repair concept, devices have a modular design and repairs can be carried out by Endress+Hauser Service or by properly trained customers. Spare parts are grouped into logical kits with the associated replacement instructions.
Repair Levelflex FMP50 PROFIBUS PA 14.2 Spare parts • Some replaceable measuring device components are identified by means of a spare part nameplate. This contains information about the spare part. • In the connection compartment cover of the device there is a spare part nameplate which contains the following information: •...
Levelflex FMP50 PROFIBUS PA Accessories Accessories 15.1 Device-specific accessories 15.1.1 Weather protection cover The weather protection cover can be ordered together with the device via the "Accessory enclosed" product structure. A0015466 27 Height. Unit of measurement mm (in) 299 (11.8) 202 (7.95)
Levelflex FMP50 PROFIBUS PA Accessories 15.1.3 Mounting kit, insulated Accessories Description Mounting kit, insulated suitable for FMP50 A0013586 30 Scope of delivery of mounting kit: Insulation sleeve Eye bolt To secure rope probes so that they are reliably insulated.
Accessories Levelflex FMP50 PROFIBUS PA 15.1.4 Centering star Accessories Description Centering star PFA • 16.4 mm (0.65 in) • 37 mm (1.46 in) suitable for FMP50 A0014577 For probe 8 mm (0.3 in) For probes 12 mm (0.47 in) and 16 mm (0.63 in) The centering star is suitable for probes with a rod diameter of 8 mm (0.3 in),...
Accessories Levelflex FMP50 PROFIBUS PA Technical data • Resistance per channel: 2 × 0.5 Ω • Threshold DC voltage: 400 to 700 V • Threshold surge voltage: < 800 V • Capacitance at 1 MHz: < 1.5 pF • Nominal leakage current (8/20 μs): 10 kA •...
For details, see the "Special Documentation" SD02252F 15.2 Communication-specific accessories Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser Common Data Interface) and the USB port of a computer or laptop Order number: 51516983 For details, see "Technical Information" TI00405C 15.3...
Operating menu Levelflex FMP50 PROFIBUS PA Operating menu 16.1 Overview of the operating menu (display module) Navigation Operating menu Language Setup → 108 Device tag → 108 Device address → 108 Distance unit → 108 →...
Page 95
Levelflex FMP50 PROFIBUS PA Operating menu PV filter time → 116 → 117 Fail safe type Fail safe value → 117 ‣ Advanced setup → 118 Locking status → 118 Access status display → 119 Enter access code →...
Page 96
Operating menu Levelflex FMP50 PROFIBUS PA ‣ Edit table Level Customer value Activate table → 134 ‣ Safety settings → 135 Output echo lost → 135 → 135 Value echo lost Ramp at echo lost → 136 Blocking distance →...
Page 97
Levelflex FMP50 PROFIBUS PA Operating menu Switch-off value → 146 → 147 Switch-off delay Failure mode → 147 Switch status → 147 Invert output signal → 147 ‣ Display → 149 Language → 149 Format display →...
Levelflex FMP50 PROFIBUS PA Operating menu 16.2 Overview of the operating menu (operating tool) Navigation Operating menu Setup → 108 → 108 Device tag Device address → 108 Distance unit → 108 Tank type →...
Page 102
Operating menu Levelflex FMP50 PROFIBUS PA Fail safe type → 117 Fail safe value → 117 ‣ → 118 Advanced setup Locking status → 118 Access status tooling → 118 Enter access code → 119 ‣...
Page 103
Levelflex FMP50 PROFIBUS PA Operating menu Level → 134 → 134 Customer value Activate table → 134 ‣ Safety settings → 135 Output echo lost → 135 Value echo lost → 135 Ramp at echo lost →...
Page 104
Operating menu Levelflex FMP50 PROFIBUS PA Failure mode → 147 Switch status → 147 → 147 Invert output signal ‣ Display → 149 Language → 149 Format display → 149 → 151 Value 1 to 4 display Decimal places 1 to 4 →...
Page 105
Levelflex FMP50 PROFIBUS PA Operating menu Backup state → 156 → 156 Comparison result ‣ Administration → 158 Define access code Device reset → 158 Diagnostics → 161 Actual diagnostics → 161 Timestamp →...
Page 106
Operating menu Levelflex FMP50 PROFIBUS PA ‣ Measured values → 167 Distance → 111 → 131 Level linearized Terminal voltage 1 → 168 Switch status → 147 ‣ Analog inputs ‣ → 169 Analog input 1 to 6 Channel →...
Page 107
Levelflex FMP50 PROFIBUS PA Operating menu Last check time → 178 → 179 Level signal Launch signal → 179 ‣ Heartbeat → 180 Endress+Hauser...
Operating menu Levelflex FMP50 PROFIBUS PA 16.3 "Setup" menu • : Indicates how to navigate to the parameter using the display and operating module • : Indicates how to navigate to the parameter using operating tools (e.g. FieldCare) • : Indicates parameters that can be locked via the access code.
Levelflex FMP50 PROFIBUS PA Operating menu Selection • Metallic • Bypass / pipe • Non metallic • Mounted outside • Coaxial Factory setting Depending on the probe Additional information • Depending on the probe some of the options mentioned above may not be available or there may be additional options.
Operating menu Levelflex FMP50 PROFIBUS PA Empty calibration Navigation Setup → Empty calibr. Description Distance process connection to min. level. User entry Depending on the probe Factory setting Depending on the probe Additional information A0013178 31 Empty calibration (E) for level measurements in liquids Full calibration ...
Levelflex FMP50 PROFIBUS PA Operating menu Additional information 100% A0013186 32 Full calibration (F) for level measurements in liquids Level Navigation Setup → Level Description Displays measured level L (before linearization). Additional information A0013194 33 Level in case of liquid measurements The unit is defined in the Level unit parameter (→...
Operating menu Levelflex FMP50 PROFIBUS PA Additional information A0013198 34 Distance for liquid measurements The unit is defined in the Distance unit parameter (→ 108). Signal quality Navigation Setup → Signal quality Description Displays the signal quality of the evaluated echo.
Page 113
Levelflex FMP50 PROFIBUS PA Operating menu Confirm distance Navigation Setup → Confirm distance Description Specify, whether the measured distance matches the real distance. Depending on the selection the device automatically sets the range of mapping. Selection • Manual map •...
Page 114
Operating menu Levelflex FMP50 PROFIBUS PA Present mapping Navigation Setup → Present mapping Description Indicates up to which distance a mapping has already been recorded. Mapping end point Navigation Setup → Map. end point Prerequisite Confirm distance (→ 113) = Manual map or Distance too small Description Specify new end of the mapping.
Levelflex FMP50 PROFIBUS PA Operating menu 16.3.1 "Mapping" wizard The Mapping wizard is only available when operating via the local display. When operating via an operating tool, all parameters concerning the mapping are located directly in the Setup menu (→ 108).
Operating menu Levelflex FMP50 PROFIBUS PA 16.3.2 "Analog input 1 to 6" submenu There is an Analog input submenu for each AI block of the device. The AI block is used to configure the measured value transmission to the bus.
Levelflex FMP50 PROFIBUS PA Operating menu Additional information This parameter defines the damping constant τ (in seconds) for the output of the Analog Input Block. Fail safe type Navigation Expert → Analog inputs → Analog input 1 to 6 → Fail safe type...
Operating menu Levelflex FMP50 PROFIBUS PA 16.3.3 "Advanced setup" submenu Navigation Setup → Advanced setup Locking status Navigation Setup → Advanced setup → Locking status Description Indicates the write protection with the highest priority that is currently active.
• If no key is pressed for 10 minutes or the user goes from the navigation and editing mode back to the measured value display mode, the device automatically locks the write- protected parameters after another 60 s. Please contact your Endress+Hauser Sales Center if you lose your access code. Endress+Hauser...
Operating menu Levelflex FMP50 PROFIBUS PA "Level" submenu Navigation Setup → Advanced setup → Level Medium type Navigation Setup → Advanced setup → Level → Medium type Description Specify type of medium. User interface • Liquid • Solid...
• Dielectric constant (DC value) Compendium CP01076F • The Endress+Hauser "DC Values app" (available for Android and iOS) If EOP level evaluation = Fix DC, the exact dielectric constant must be specified in the DC value parameter. The Medium property parameter therefore does not apply in this case.
Operating menu Levelflex FMP50 PROFIBUS PA For "Operating mode" = "Level" and "Medium type" = "Solid" Process property Step response time / s Very fast > 100 m (333 ft) /h Fast > 10 m (33 ft) /h Standard < 10 m (33 ft) /h Medium <...
Levelflex FMP50 PROFIBUS PA Operating menu Level unit Navigation Setup → Advanced setup → Level → Level unit Description Select level unit. Selection SI units US units • % • ft • m • in • mm Additional information The level unit may differ from the distance unit defined in the Distance unit parameter (→...
Operating menu Levelflex FMP50 PROFIBUS PA A0013219 35 Blocking distance (UB) for liquid measurements Level correction Navigation Setup → Advanced setup → Level → Level correction Description Specify level correction (if required). User entry –200 000.0 to 200 000.0 % Additional information The value specified in this parameter is added to the measured level (before linearization).
Page 125
Levelflex FMP50 PROFIBUS PA Operating menu "Linearization" submenu 100% L‘ I‘ L‘ 100% L‘1 L‘2 L‘ 100% L‘ 100% L‘ 100% L‘ 100% L‘ 100% L‘ A0016084 36 Linearization: Conversion of the level and, if applicable, interface into a volume or a weight; the...
Operating menu Levelflex FMP50 PROFIBUS PA Structure of the submenu on the local display Navigation Setup → Advanced setup → Linearization ‣ Linearization Linearization type Unit after linearization Free text Maximum value Diameter Intermediate height Table mode ‣ Edit table...
Page 127
Levelflex FMP50 PROFIBUS PA Operating menu Structure of the submenu in the operating tool (e.g. FieldCare) Navigation Setup → Advanced setup → Linearization ‣ Linearization Linearization type Unit after linearization Free text Level linearized Maximum value Diameter Intermediate height...
Levelflex FMP50 PROFIBUS PA Operating menu Meaning of the options • None The level is output in the level unit without being converted (linearized) beforehand. • Linear The output value (volume/weight) is proportional to the level L. This applies, for example, to vertical cylindrical tanks and silos.
Levelflex FMP50 PROFIBUS PA Operating menu User entry Up to 32 alphanumerical characters (letters, numbers, special characters) Level linearized Navigation Setup → Advanced setup → Linearization → Level linearized Description Displays linearized level. Additional information The unit is defined by the Unit after linearization parameter → 129.
Operating menu Levelflex FMP50 PROFIBUS PA Intermediate height Navigation Setup → Advanced setup → Linearization → Intermed. height Prerequisite Linearization type (→ 128) has one of the following values: • Pyramid bottom • Conical bottom • Angled bottom...
Page 133
Levelflex FMP50 PROFIBUS PA Operating menu Conditions the linearization table must meet: • The table may consist of up to 32 pairs of values "Level - Linearized Value". • The table must be monotonic (monotonically increasing or decreasing). • The first linearization point must refer to the minimum level.
Levelflex FMP50 PROFIBUS PA Operating menu "Safety settings" submenu Navigation Setup → Advanced setup → Safety sett. Output echo lost Navigation Setup → Advanced setup → Safety sett. → Output echo lost Description Output signal in case of a lost echo.
Operating menu Levelflex FMP50 PROFIBUS PA Ramp at echo lost Navigation Setup → Advanced setup → Safety sett. → Ramp echo lost Prerequisite Output echo lost (→ 135) = Ramp at echo lost Description Slope of the ramp in the case of a lost echo...
Page 137
Levelflex FMP50 PROFIBUS PA Operating menu due to a level change during operation. Signals which are already in the blocking distance when the device is switched on, are ignored. This behavior is only valid if the following two conditions are met: •...
Operating menu Levelflex FMP50 PROFIBUS PA "WHG confirmation" wizard The WHG confirmation wizard is only available for devices with WHG approval (Feature 590: "Additional Approval", option LC: "WHG overfill prevention" ) which are currently not in the WHG-locked state. The WHG confirmation wizard is used to lock the device according to WHG. For details refer to the "Functional Safety Manual"...
Levelflex FMP50 PROFIBUS PA Operating menu "Deactivate WHG" wizard The Deactivate WHG wizard (→ 139) is only visible if the device is WHG-locked. For details refer to the "Functional Safety Manual" of the respective device. Navigation Setup → Advanced setup → Deactivate WHG Reset write protection ...
Operating menu Levelflex FMP50 PROFIBUS PA "Probe settings" submenu The Probe settings submenu helps to ensure that the end of probe signal within the envelope curve is correctly assigned by the evaluation algorithm. The assignment is correct if the length of probe indicated by the device matches the acutal lenght of the probe. The automatic probe length correction can only be performed if the probe is installed in the vessel and is completely uncovered (no medium).
Levelflex FMP50 PROFIBUS PA Operating menu Confirm probe length Navigation Setup → Advanced setup → Probe settings → Confirm length Description Select, whether the value displayed in the Present probe length parameter → 140 matches the actual length of the probe. Based on this input, the device performs a probe length correction.
Page 142
Operating menu Levelflex FMP50 PROFIBUS PA "Probe length correction" wizard The Probe length correction wizard is only available when operating via the local display. When operating via an operating tool, all parameters concerning the probe length correction are located directly in the Probe settings submenu (→ 140).
Operating menu Levelflex FMP50 PROFIBUS PA Selection • Off • Digital output AD 1 • Digital output AD 2 • Digital output 1 • Digital output 2 • Digital output 3 • Digital output 4 Additional information The Digital output AD 1 and Digital output AD 2 options refer to the Advanced Diagnostic Blocks.
Levelflex FMP50 PROFIBUS PA Operating menu Switch-on value Navigation Setup → Advanced setup → Switch output → Switch-on value Prerequisite Switch output function (→ 143) = Limit Description Enter measured value for the switch-on point. User entry...
Levelflex FMP50 PROFIBUS PA Operating menu Switch-off delay Navigation Setup → Advanced setup → Switch output → Switch-off delay Prerequisite • Switch output function (→ 143) = Limit • Assign limit (→ 144) ≠ Off Description Define delay for the switch-off of status output.
Page 148
Operating menu Levelflex FMP50 PROFIBUS PA Additional information Meaning of the options • No The behavior of the switch output is as described above. • Yes The states Open and Closed are inverted as compared to the description above. Endress+Hauser...
Levelflex FMP50 PROFIBUS PA Operating menu "Display" submenu Display submenu is only visible if a display module is connected to the device. Navigation Setup → Advanced setup → Display Language Navigation Setup → Advanced setup → Display → Language Description Set display language.
Page 150
Operating menu Levelflex FMP50 PROFIBUS PA Additional information 4841.000 Â A0019963 39 "Format display" = "1 value, max. size" Â 93.5 % Â 159.0 A0019964 40 "Format display" = "1 bargraph + 1 value" Â 93.5 Â 159.0 A0019965 ...
Levelflex FMP50 PROFIBUS PA Operating menu Value 1 to 4 display Navigation Setup → Advanced setup → Display → Value 1 display Description Select the measured value that is shown on the local display. Selection • Level linearized •...
Operating menu Levelflex FMP50 PROFIBUS PA User entry 1 to 10 s Additional information This parameter is only relevant if the number of selected measuring values exceeds the number of values the selected display format can display simultaneously. Display damping ...
Levelflex FMP50 PROFIBUS PA Operating menu Additional information The number of characters which can be displayed depends on the characters used. Separator Navigation Setup → Advanced setup → Display → Separator Description Select decimal separator for displaying numerical values.
Operating menu Levelflex FMP50 PROFIBUS PA Backlight Navigation Setup → Advanced setup → Display → Backlight Prerequisite The device has the SD03 local display (with optical keys). Description Switch the local display backlight on and off. Selection • Disable •...
Levelflex FMP50 PROFIBUS PA Operating menu "Configuration backup display" submenu This submenu is only visible if a display module is connected to the device. The configuration of the device can be saved to the display module at a certain point of time (backup).
Page 156
Operating menu Levelflex FMP50 PROFIBUS PA Additional information Meaning of the options • Cancel No action is executed and the user exits the parameter. • Execute backup A backup copy of the current device configuration in the HistoROM (built-in in the device) is saved to the display module of the device.
Page 157
Levelflex FMP50 PROFIBUS PA Operating menu Additional information Meaning of the display options • Settings identical The current device configuration of the HistoROM is identical to the backup copy in the display module. • Settings not identical The current device configuration of the HistoROM is not identical to the backup copy in the display module.
Page 158
Enter access code parameter (→ 119). Please contact your Endress+Hauser Sales Center if you lose the access code. If operating via the local display: the new access code is only valid once it has been confirmed in the Confirm access code parameter (→...
Page 159
Levelflex FMP50 PROFIBUS PA Operating menu • Of customer settings All customer parameters are reset to their factory setting. Service parameters, however, remain unchanged. • To transducer defaults Every measurment-related parameter is reset to its factory setting. Service parameters and communication-related parameters, however, remain unchanged.
Page 160
Operating menu Levelflex FMP50 PROFIBUS PA "Define access code" wizard The Define access code wizard is only available when operating via the local display. When operating via an operating tool, the Define access code parameter is located directly in the Administration submenu. The Confirm access code parameter is not available for operation via operating tool.
Levelflex FMP50 PROFIBUS PA Operating menu 16.4 "Diagnostics" menu Navigation Diagnostics Actual diagnostics Navigation Diagnostics → Actual diagnos. Description Displays current diagnostic message. Additional information The display consists of: • Symbol for event behavior • Code for diagnostic behavior •...
Page 162
Operating menu Levelflex FMP50 PROFIBUS PA Timestamp Navigation Diagnostics → Timestamp Operating time from restart Navigation Diagnostics → Time fr. restart Description Displays the time the device has been in operation since the last device restart. Operating time Navigation ...
Levelflex FMP50 PROFIBUS PA Operating menu 16.4.1 "Diagnostic list" submenu Navigation Diagnostics → Diagnostic list Diagnostics 1 to 5 Navigation Diagnostics → Diagnostic list → Diagnostics 1 Description Display the current diagnostics messages with the highest to fifth-highest priority.
Operating menu Levelflex FMP50 PROFIBUS PA 16.4.2 "Event logbook" submenu The Event logbook submenu is only available when operating via the local display. When operating via FieldCare, the event list can be displayed in the FieldCare function "Event List / HistoROM".
Shows the serial number of the measuring device. Additional information Uses of the serial number • To identify the device quickly, e.g. when contacting Endress+Hauser. • To obtain specific information on the device using the Device Viewer: www.endress.com/deviceviewer The serial number is also indicated on the nameplate.
Page 166
Operating menu Levelflex FMP50 PROFIBUS PA Order code Navigation Diagnostics → Device info → Order code Description Shows the device order code. User interface Character string comprising numbers, letters and special characters Additional information The order code is generated from the extended roder code, which defines all device features of the product structure.
Levelflex FMP50 PROFIBUS PA Operating menu 16.4.4 "Measured values" submenu Navigation Diagnostics → Measured val. Distance Navigation Diagnostics → Measured val. → Distance Description Displays the measured distance D between the reference point (lower edge of the flange or threaded connection) and the level.
Operating menu Levelflex FMP50 PROFIBUS PA Terminal voltage 1 Navigation Diagnostics → Measured val. → Terminal volt. 1 Switch status Navigation Diagnostics → Measured val. → Switch status Description Shows the current switch output status. Endress+Hauser...
Levelflex FMP50 PROFIBUS PA Operating menu 16.4.5 "Analog input 1 to 6" submenu There is an Analog input submenu for each Analog Input Block of the device. Only the most important parameters of the respective block are available at this position of the operating menu.
Operating menu Levelflex FMP50 PROFIBUS PA Additional information • For Mode block actual = Man: Enter the output value of the Analog Input Block. • Else: Displays the output value of the Analog Input Block. Out status Navigation Diagnostics → Analog inputs → Analog input 1 to 6 → Out status...
Operating menu Levelflex FMP50 PROFIBUS PA Additional information This parameter defines the interval between the individual data points in the data log, and thus the maximum loggable process time T • If 1 logging channel is used: T = 1000 ⋅ t •...
Page 173
Levelflex FMP50 PROFIBUS PA Operating menu "Display channel 1 to 4" submenu The Display channel 1 to 4 submenus are only available for operation via the local display. When operating via FieldCare, the logging diagram can be displayed in the FieldCare function "Event List / HistoROM"...
Operating menu Levelflex FMP50 PROFIBUS PA 16.4.7 "Simulation" submenu The Simulation submenu is used to simulate specific measuring values or other conditions. This helps to check the correct configuration of the device and connected control units. Conditions which can be simulated...
Levelflex FMP50 PROFIBUS PA Operating menu Switch status Navigation Expert → Diagnostics → Simulation → Switch status Prerequisite Switch output simulation (→ 176) = On Description Select the status of the status output for the simulation. Selection •...
Operating menu Levelflex FMP50 PROFIBUS PA 16.4.8 "Device check" submenu Navigation Diagnostics → Device check Start device check Navigation Diagnostics → Device check → Start dev. check Description Start a device check. Selection • No • Yes Additional information In the case of a lost echo a device check can not be performed.
Page 179
Levelflex FMP50 PROFIBUS PA Operating menu Level signal Navigation Diagnostics → Device check → Level signal Prerequisite Device check has been performed. Description Displays result of the device check for the level signal. User interface • Check not done •...
Operating menu Levelflex FMP50 PROFIBUS PA 16.4.9 "Heartbeat" submenu The Heartbeat submenu is only available via FieldCare or DeviceCare. It contains the wizards which are part of the Heartbeat Verification and Heartbeat Monitoring application packages. Detailed description SD01872F Navigation Diagnostics → Heartbeat...