Electrical installation

9.3.6 To connect the alarm output

Installer reference guide
104
B
A
B
3 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
[9.D] Alarm output
1 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
2 Connect the alarm output cable to the appropriate terminals as shown in the
illustration below.
2
1
X2M
7
9
A4P
Y1
YC
A
1 2
X2M
"7.2.5 To open the indoor
1+2
Wires connected to the alarm output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.
3
7
4
unit" [
 55]):
Y1
EPRA14~18DAV3+W1 + ETVZ16S18+23EA6V+9W
Daikin Altherma 3 H HT F
4P644739-1 – 2021.02
1
3
2