Using the keypad with settings and parameters
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests, and Alarms:
• Navigate to the desired menu.
• Press the  button (Enter) to display the first item in
the currently displayed menu.
• Use the  and  buttons to scroll to the desired
parameter.
• Press the  button (Enter) to display the value of the
• Press the  button to increase (change) the displayed
1
parameter value.
• Press the  button to decrease (change) the displayed
parameter value.
• Press the  button to accept the displayed value and
store it in non-volatile RAM.
• CHANGE STORED displays.
• Press the  button (MenuUp/Exit) to return to the
previous menu.
Menu structure
The Menus in display order are:
• STATUS
• SETPOINTS
1. When values are displayed, pressing and holding the  and
button causes the display to automatically increment.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
Figure 11: Single enthalpy curve and boundaries
Johnson Controls Ducted Systems
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
NOTE: Your menu parameters will be different depending on
your configuration. See the JADE™ Economizer
Module accessory instruction P/N 1150208-UAI-A-0514
included in this instruction packet for additional menu
information.
Economizer setup and configuration
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed system.
NOTE: During setup, the Economizer module is live at all
times.
The setup process uses a hierarchical menu structure that is
easy to use. You press the  and  arrow buttons to move
forward and backward through the menus and press the 
button to select and confirm setup item changes.
Time-out and screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
P2 (T,RH)
ES5
5725848-XIM-A-0319
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P1 (T,RH)
ES4
ES3
ES2
ES1
HL
23