Operation; Cooling Sequence Of Operation - York ZF076 Installation Manual

Hide thumbs Also See for ZF076:
Table of Contents

Advertisement

Figure 21: Pressure drop across coil

Operation

Cooling sequence of operation

ZF units have either a Simplicity Lite or a Smart Equipment™
Control Board. Both control boards work in a similar fashion, as
out lined below.
For the ZF series of units, the thermostat makes a circuit
between "R" and "Y1" for the first stage of cooling.
The call is passed to the Unit Control Board (UCB), which
then determines whether the requested operation is available
and, if so, which components to energize.
For gas heating, the UCB monitors the "W1" call but does not
handle the operation of the gas furnace. An ignition control
board controls the gas heater operation. For electric heat units,
the UCB passes the call to the electric heater. In both cases,
when the "W1" call is sensed, the indoor air blower is energized
following a specified heating delay.
If at any time a call for both heating and cooling are present, the
heating operation will be performed. If operating, the cooling
system is halted as with a completion of a call for cooling.
Heating always takes priority.
Continuous blower
By setting the room thermostat fan switch to "ON," the supply
air blower will operate continuously.
Intermittent blower
With the room thermostat fan switch set to "AUTO" and the
system switch set to either the "AUTO" or "HEAT" settings, the
blower is energized whenever a cooling or heating operation is
requested. The blower is energized after any specified delay
associated with the operation.
When energized, the indoor blower has a minimum run time of
30 seconds. Additionally, the indoor blower has a delay of 10
seconds between operations.
Johnson Controls Ducted Systems
No outdoor air options
When the thermostat calls for cooling, the low-voltage control
circuit from "R" to "Y1" and "G" is completed. The compressor and
condenser fan motor are energized. After completing the specified
fan on delay for cooling, the UCB will energize the blower motor.
Once the thermostat has been satisfied, it will de-energize Y1. If
the compressor has satisfied its minimum run time, the
compressor and condenser fan de-energize. Otherwise, the
unit operates the cooling system until the minimum run time for
the compressor has been completed. After the compressor de-
energizes, the blower is stopped following the elapse of the fan
off delay for cooling.
To be available, a compressor must not be locked-out due to a
high or low-pressure switch or freezestat trip Simplicity Lite
Control or Evaporator Low Limit sensor detecting a temperature
below 26° F Smart Equipment™ Control and the anti-short
cycle delay (ASCD) must have elapsed.
Economizer with single enthalpy sensor (Simplicity Lite) or
Economizer with dry bulb sensor (Smart Equipment™)
When the room thermostat calls for cooling, the low voltage
control circuit from "R" to "G" and "Y1" is completed. The UCB
energizes the blower motor (if the fan switch on the room
thermostat is set in the "AUTO" position) and drives the
economizer dampers from fully closed to their minimum position.
If the enthalpy (Simplicity Lite) or Dry bulb temperature (Smart
Equipment™) of the outdoor air is below the setpoint of the
enthalpy or dry bulb controller (previously determined), "Y1"
energizes the economizer. The dampers will modulate to
maintain a constant supply air temperature as monitored by the
discharge air sensor. If the outdoor air enthalpy (Simplicity Lite)
or dry bulb temperature (Smart Equipment™) is above the
setpoint, "Y1" energizes the compressor and condenser fan
motor only.
Once the thermostat has been satisfied, it will de-energize "Y1". If
the compressor has satisfied its minimum run time, the
compressor and condenser fan are de-energized. Otherwise, the
unit operates the cooling system until the minimum run times for
the compressor has been completed. After the compressor de-
energizes, the blower is stopped following the elapse of the fan
off delay for cooling, and the economizer damper goes to the
closed position. If the unit is in continues fan operation the
economizer damper goes to the min. position.
Economizer with dual enthalpy sensors
The operation with the dual enthalpy sensors is identical to the
single sensor except that a second enthalpy sensor is mounted
in the return air. This return air sensor allows the economizer to
choose between outdoor air and return air, whichever has the
lowest enthalpy value, to provide maximum operating efficiency.
Economizer with power exhaust
A unit equipped with an economizer (dry bulb single or dual
enthalpy) and a power exhaust operates as specified above
with one addition. The power exhaust motor is energized 45
seconds after the actuator position exceeds the exhaust fan set
point on the economizer control. When the power exhaust is
5725848-XIM-A-0319
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zf036Zf048Zf060Zf series

Table of Contents