Pcs45/Pcl45Usb Configurator For Mtl Temperature Converters - Eaton Crouse-Hinds MTL5500 Series Instruction Manual

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

6 .9

PCS45/PCL45USB configurator for MTL temperature converters

The PCS45/PCL45USB configurator allows MTL isolating temperature converters to be configured
from a standard PC running a Microsoft® Windows® operating system. The configurator comprises
PC software provided on a CD (PCS45), and an ATEX certified interfacing link (PCL45USB).
Temperature converters can be configured from the safe area, while on-line, and the software allows
configurations to be saved to disk and printed out when required.
Safe area
It is suitable for use with MTL4000, MTL4500, MTL5000 and MTL5500 products.
PCL45USB hardware
The PCL45USB provides the interfacing link between the converter module and the PC running
the software and connects to the PC using the USB cable provided. The PCL45USB has a built-in
cable fitted with a 3.5mm jackplug to connect to the 'Config' socket on MTL4500 and MTL5500
converters. An adapter cable is also provided to accommodate our earlier converters.
PCS45 Configuration software
The software provided on the CD requires only approximately 20Mb of hard disk space and is
compatible with Windows 2000, Windows XP or Windows 7 . Ensure that the chosen PC has a CD
ROM drive and an available USB port. A local or network printer may also be an advantage.
Safety
It is not permitted to connect the PCL45USB to any device other than one approved by Eaton.
Authorisation is valid provided that the converter type is named on the PCL45USB certificate or if
the PCL45USB is specified on the converter certificate. Repairs to the PCL45USB are not permitted.
Setting up
The equipment can be used only in the safe area.
Before plugging in the PCL45USB link to the computer, extract the USB driver files to a known
location on your PC. Afterwards, plug in the PCL45USB to the USB port on the PC and wait for
it to find the new device. When requested by the computer, show it the location of the driver
files so that it can complete the device installation.
Place the PCS45 software CD in the computer's CDROM drive and follow the on-screen
instructions to install the software.
The PCL45USB is powered from the data lines and quickly establishes communication after
plugging the 3.5mm connector to the device socket.
Note: Ensure that the 3.5mm jack plug is fully inserted into the socket of the temperature converter.
The software and its operations manual (INM PCS45) is available on-line at:
http://www.mtl-inst.com/product/configuration_tools_and_software/
58
INM 5500 Rev 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents