Mtl5523 - Solenoid Alarm Driver - Eaton Crouse-Hinds MTL5500 Series Instruction Manual

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

6 .2 .3
Single channel, with line-fault detection, IIC
The MTL5523 interface controls an on/off device in a hazardous area using a volt-free contact
or logic signal in the safe area, and is suitable for driving loads such as solenoids. Line-Fault
Detection (LFD) operates independently of the output state and is signalled by a safe-area,
solid-state switch output which, when a field line is open or short-circuited, becomes de-
energised. Earth-fault detection can be provided by connecting an MTL4220 earth leakage
detector to terminal 3.
LFD
STS
MTL5523
PWR
Figure 6 .12:
Top label
for MTL5523
32

MTL5523 - Solenoid Alarm driver

Hazardous area
+
Solenoid, alarm
or other IS device
Terminal
Function
1
Output –ve
2
Output +ve
7
Line fault signal -ve
8
Phase reversal link
9
Phase reversal link
10
Line fault signal +ve
11
Control –ve
12
Control +ve
13
Supply –ve
14
Supply +ve
Safe area
6
7
5
8
4
9
3
10
2
11
1
12
13
14
20 to 35V dc
‡ link to reverse output phase
LFD
Control
Vs–
Vs+
INM 5500 Rev 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents