Mtl5523V/Mtl5523Vl - Solenoid Alarm Driver - Eaton Crouse-Hinds MTL5500 Series Instruction Manual

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

6 .2 .4
Single channel, voltage controlled with line-fault detection, IIC
With the MTL5523V or MTL5523VL interface, an on/off device in a hazardous area can be
controlled by a voltage signal in the safe area. It is suitable for driving loads such as solenoids.
Line fault detection (LFD), which operates irrespective of the output state, is signalled by a safe-
area, solid-state switch which energises if a field line is open or short–circuited.
The VL version has a lower current capability to suit alternative load requirements - see datasheet.
STS
MTL5523V
PWR
STS
MTL5523VL
PWR
Figure 6 .13:
Top labels
for MTL5523V
& MTL5523VL
33

MTL5523V/MTL5523VL - Solenoid Alarm driver

Hazardous area
Safe area
6
5
4
3
+
2
Solenoid, alarm
or other IS device
Terminal
Function
1
Output –ve
2
Output +ve
7, 8, 9
Line fault signal –ve
10
Line fault signal +ve
11
Control –ve
12
Control +ve
13
Supply –ve
14
Supply +ve
7
8
9
10
11
12
1
13
14
20 to 35V dc
LFD
Control
V
Vs–
Vs+
INM 5500 Rev 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents