Mtl5544D - Repeater Power Supply - Eaton Crouse-Hinds MTL5500 Series Instruction Manual

Isolating interface units
Hide thumbs Also See for Crouse-Hinds MTL5500 Series:
Table of Contents

Advertisement

6 .4 .5
Two channel, for 4/20mA HART® for 2- or 3-wire transmitters, two outputs
The MTL5544D provides a fully-floating dc supply for energising a conventional 2- or 3-wire
4/20mA transmitter located in a hazardous area, and repeats the current in other circuits
to drive two safe-area loads. For HART 2-wire transmitters, the unit allows bi-directional
transmission of digital communication signals superimposed on the 4/20mA loop current via
channel 1 only,Separately powered current sources, such as 4-wire transmitters, can be
connected but will not support HART communication.
MTL5544D
PWR
Figure 6 .24:
Top label
for MTL5544D
NOTE: For correct operation of the module, a suitable load must be present on both output channels.
This is of particular importance during testing, commissioning or maintenance activities when the
temporary disconnection, or absence, of a load can affect the transfer accuracy of the analogue variable.
46

MTL5544D - Repeater Power Supply

Hazardous area
Com
Input
4/20mA
Terminal
Function
1
Current input
2
Transmitter supply +ve
3
Common
7
Ch2 output +ve via 220Ω HART not supported.
8
Ch2 output –ve
9
Ch2 output +ve
10
Ch1 output +ve via 220Ω for HART apps.
11
Ch1 output –ve
12
Ch1 output +ve
13
Supply –ve
14
Supply +ve
Safe area
6
7
I
5
8
4
9
I
10
3
Tx+
11
2
I
12
1
13
14
Ch 2
4/20mA
+
Load
Ch 1
4/20mA
+
Load
Vs–
Vs+
20 to 35V dc
INM 5500 Rev 11