THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
9070
Dehumidification -
Overcooling Limit
9080
Dehumidification
Control
9090
Dehumidification
Minimum On Time
9100
High Humidity
Comfort Reset
Setting
68-0311—07
®
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
0°, 1°, 2°, 3° F
Basic
Minimum On Time
High Humidity Comfort Reset
High Humidity Comfort Reset with
Minimum On Time
Reheat
Reheat with Minimum On Time
5 to 15 minutes
1° F to 5° F
IAQ WITH EIM
Residential,
Commercial
Default
or Both
3° F
Residential
Basic
Commercial
10 minutes
Commercial
2° F
Commercial
56
Requires
EIM
Notes
No
This ISU is only displayed when ISU 9000
Dehumidification Equipment is set to A/C with
Low Speed Fan or A/C with High Speed Fan.
The thermostat uses the cooling system to
reduce humidity by lowering the temperature
up to 3° F below the current cool setpoint until
the desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
0° F is only an option when ISU 9000
Dehumidification Equipment is set to A/C with
Low Speed Fan.
No
See "Dehumidification - Commercial"
beginning on page 110.
No
This option ensures that the compressor runs
long enough to effectively reduce humidity
when the cooling equipment is cycled on. The
compressor will run for the "minimum on time"
you set until the desired humidity level is
reached.
No
The thermostat uses the cooling system to
reduce humidity by lowering the temperature
up to 5° F below the current cool setpoint until
the desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.