Honeywell Prestige 2.0 THX9421 Manual page 64

Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
13130
Allow Cool Delta T
Diagnostics when
Indoor Temperature
is [Indoor
Temperature Range]
13130
13140
Allow Cool Delta T
Diagnostics when
Indoor Humidity is
[Indoor Humidity
Range]
13140
13150
Allow Cool Delta T
Diagnostics when
Outdoor
Temperature is
[Outdoor
Temperature Range]
13150
13160
Allow Cool Delta T
Diagnostics when
Outdoor Humidity is
[Outdoor Humidity
Range]
13160
13170
Defrost Cycle
13180
Delta T Alert
Sensitivity
68-0311—07
®
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Minimum Setting
No Limit
35° F to 115° F (in 5° F
increments)
Maximum Setting
No Limit
40° F to 120° F (in 5° F
increments)
Minimum Setting
No Limit
0% to 95% (in 5% increments)
Maximum Setting
No Limit
5% to 100% (in 5% increments)
Minimum Setting
No Limit
-50° F to 135° F (in 5° F
increments)
Maximum Setting
No Limit
-45° F to 140° F (in 5° F
increments)
Minimum Setting
No Limit
0% to 95% (in 5% increments)
Maximum Setting
No Limit
5% to 100% (in 5% increments)
None
1 to 60 minutes (in 1 minute
increments)
1 to 5
IAQ WITH EIM
Residential,
Commercial
Default
or Both
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
No Limit
Both
(Always)
10
Both
3
Both
64
Requires
EIM
Notes
Yes
This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015 Set
Advanced Diagnostic Options is set to Yes.
The thermostat monitors Delta T of the system
Yes
ONLY when the indoor temperature is within a
certain range. Set to No Limit to monitor Delta
T during all indoor temperature conditions.
Yes
This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015 Set
Advanced Diagnostic Options is set to Yes.
Yes
The thermostat monitors Delta T of the system
ONLY when the indoor humidity is within a
certain range. Set to No Limit to monitor Delta
T during all indoor humidity conditions.
Yes
This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015 Set
Advanced Diagnostic Options is set to Yes.
The thermostat monitors Delta T of the system
Yes
ONLY when the outdoor temperature is within a
certain range. Set to No Limit to monitor Delta
T during all outdoor temperature conditions.
Yes
This ISU only applies to Cooling.
This ISU is only displayed when ISU 13015 Set
Advanced Diagnostic Options is set to Yes.
Yes
The thermostat monitors Delta T of the system
ONLY when the outdoor humidity is within a
certain range. Set to No Limit to monitor Delta
T during all outdoor humidity conditions.
Yes
This ISU is only displayed if ISU 2010 Heating
Equipment Type is Air to Air Heat Pump.
Press the up/down arrows to set the maximum
time duration of a defrost cycle. Check the heat
pump documentation for the defrost cycle time.
Note: The diagnostic algorithm detects when
the system goes into defrost based on the
measured Delta T of the system. When the
thermostat detects this change in temperature,
the thermostat will not compare Delta T to the
Minimum and Maximum Delta T Fault Limits.
After the defrost cycle has ended, the
thermostat will resume monitoring Delta T of
the system.
Yes
See "Delta T Alert Sensitivity (ISU 13180)."
beginning on page 89.