To Connect The Domestic Hot Water Pump; To Connect The Alarm Output - Daikin ETSXB16E7 Installation Manual

Hide thumbs Also See for ETSXB16E7:
Table of Contents

Advertisement

6 Electrical installation
A
B
5 6 9 10
X 5M
1
3 Fix the cable with cable ties to the cable tie mountings. General
information, see
"6.3.1  To connect the electrical wiring to the
unit" [ 4  17].
indoor
6.3.7

To connect the domestic hot water pump

Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC,
1 A (continuous)
[9.2.2] DHW pump
[9.2.3] DHW pump schedule
1 Open the following (see
"4.2.1 To open the indoor
1 User interface panel
2 Switch box
3 Switch box cover
4 Top cover
2 Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.
Installation manual
22
A
B
5 6 9 10
S2S
S3S
A
B
3 Fix the cable with cable ties to the cable tie mountings. General
information, see
indoor
6.3.8
Wires: (2)×0.75 mm²
Maximum load: 0.3 A, 230 V AC
Maximum load: 1 A, 5 V DC
[9.D] Alarm output
1 Open the following (see
unit" [ 4  8]):
4
1 User interface panel
3
2 Switch box
2
3 Switch box cover
1
4 Top cover
2 Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.
7 8
X 2M
1
"6.3.1  To connect the electrical wiring to the
unit" [ 4  17].

To connect the alarm output

"4.2.1 To open the indoor
Daikin Altherma 3 H HT ECH₂O
M
M2P
1~
A
B
unit" [ 4  8]):
4
3
2
1
ETSH/X(B)16P30+50E
4P679468-1B – 2022.09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 h ht ech2oEtsh16e7

Table of Contents