System Configuration and Functions
To enable the muting function, D1 and d1 must satisfy formulas (1) and (2), respectively.
This distance must prevent the muting function from being enabled by a person passing through the
muting sensors.
Also, install the F3SJ-B and muting sensors so that each workpiece passes through all muting sensors
before the next workpiece arrives at the first muting sensor.
<Wiring diagram>
Using a photoelectric switch as a muting sensor
* Two-wire type muting sensor cannot be used.
<Timing chart>
Muting sensor A1
Muting sensor B1
Muting state
Auxiliary output
F3SJ-B Unblocked
/Blocked
Safety output
Variable
T1min
T1max
T2
T3
F3SJ-E/B
30
User's Manual
B1
Reflector
A1, B1: Retro-reflective
photoelectric switch
- NPN Output
- ON when Interrupted
A1
Reflector
F3SJ-B
ON
OFF
T1min to T1max
ON
OFF
0.15 s max.
Enabled
Disabled
Blinking
OFF
Unblocked
Blocked
ON
OFF
Variable name
Muting input time limit value
(minimum)
Muting input time limit value
(maximum)
Muting time limit
Maximum muting input pulse
duration
Using an N.O contact type switch as a muting sensor
A1
T3 max.
T3 max.
T2 max.
1 Hz Blinking
Value
Minimum time difference between muting inputs 1 and 2.
0.1 s
If the time difference between muting inputs 1 and 2 is smaller
than this value, a muting error occurs.
Maximum time difference between muting inputs 1 and 2.
3 s
If the time difference between muting inputs 1 and 2 is larger than
this value, a muting error occurs.
This is the muting function continuation time.
60 s
If muting state exceeds this time, the function is canceled.
Maximum muting input time with allowable waveform cracks in
0.1 s
muting input 1 and 2.
A1, B1: N.O. contact type switch
B1
+24 VDC
Power
supply
0 V
Description