Omron Sti F3SJ-E N25 Series User Manual page 32

Table of Contents

Advertisement

System Configuration and Functions
 Wiring for auto reset mode and deactivated external device monitoring function
F39-JD A-L
S1
: External test switch (connect to 24 V if a switch is not required)
S2
: Lockout reset switch (connect to 0 V if a switch is not required)
KM1, KM2
: Safety relay with force-guided contact (G7SA) or magnetic contactor
K1
: Load or PLC, etc. (for monitoring)
*1. Use a switch for small loads (input specifications: 24 V, 1.0 mA max.).
*2. F3SJ operates even when K1 is not connected.
F3SJ-E/B
16
User's Manual
(Gray) Communication line (+)
(Pink)
Communication line (-)
S1
S2
*1
*1
F39-JD A-D
K1
KM1
KM2
*2
+24 VDC
Power
supply
0 V

Advertisement