Binary input device 16x ac 12…230 v / dc 12...115 v

Advertisement

GAMMA instabus
Technical Product Information
November 2014
Binary input device N 263E11
16x AC 12...230 V / DC 12...115 V
Installation notes
· The device can be used for permanent installation in
dry interior rooms and for insertion in control cabinets
or small distribution boards.
Υ
DANGER
· The device must only be installed and commissioned
by an authorized professional electrician.
· Unoccupied sections of DIN rail with data rail inserted
must be protected with the cover 5WG1 192-8AA01.
· When connecting the device, care should be taken that
the device can be isolated from the mains.
· The device must not be opened.
· When planning and installing electrical equipment the
relevant guidelines, regulations and specifications of
the respective country must be considered.
Technical data
Power supply
· Bus voltage: via the bus line
· Bus current: 5 mA (only half standard bus load!)
· Electronics:
- integrated power supply for AC 230V, +10%/-15%,
50 / 60 Hz
- Mains connection: 2-pole (N, L)
- power consumption: max. 1.7 W
Operating elements:
· 1 learning pushbutton:
for toggling between normal mode / addressing mode
Display elements
· 1 red LED: for checking the bus voltage and displaying
normal mode / addressing mode
· 1 green LED: for displaying the 230 V operating
voltage
1 red LED per binary input for status display;
·
LED = ON: voltage is present at the input
Inputs
· 16 inputs (each input can be connected to any phase
L1, L2 or L3 or a FELV signal)
· Input voltage: AC 12 V ... 230 V, DC 12 V ... 115 V
(U
= 0...2 V: voltage not present = log. 0;
in
U
> 9 V:
voltage present
in
Note: For DC voltage the negative pole should be con-
nected in each case to the terminal designated "N".
· Input current:
at max. AC 253 V: typically 1.5 mA (RMS)
at max. DC 127 V: typically 2.7 mA
Technical Manual
Update: http://www.siemens.de/gamma-td
2.7.4.1/2
= log. 1)
N 263E11, 4 pages
ã Siemens AG 2014
Subject to change without further notice
· Input signal delay:
- at rising edge of input signal:
max. 60 ms for DC
max. 100 ms for AC
- at falling edge of input signal:
max. 140 ms for DC
max. 100 ms for AC
· Input signal ON-time: min. 60 ms at DC
min. 100 ms at AC
· Input signal OFF-time: min. 140 ms at DC
min. 100 ms at AC
· Max. detectable switching frequency: 5 Hz
· Input function: can be selected
· Max. length of connecting cable: 100 m
Connections
· Mains connection and inputs:
- Plug-in terminals, insulation strip length 9...10 mm
·
The following conductor cross-sections are permitted:
-
0,5 ... 2.5 mm
single-core
2
-
0,5... 2.5 mm² finely stranded with plug connector,
sealed crimp connection
0,5 ... 1.5 mm³ finely stranded, with connector sleeve
-
1.0 and 1.5 mm² finely stranded, untreated
-
· KNX bus line:
- Pressure contacts on data rail,
- Screw-less bus terminal, 0.6 ... 0.8 mm Ø single-core,
insulation strip length 5 mm
Mechanical data
· Housing: plastic
· Dimensions: DIN rail mounted device in N-system di-
mensions, width 6 Module Units (1 MU = 18 mm)
· Weight: approx. 325 g
· Fire load: approx. 6113 kJ +/ -10%
· Mounting: Snap-on mounting on DIN rail
EN 60715-TH35-7.5
Electrical safety
· Degree of pollution (according to IEC 60664-1): 2
· Type of protection (according to EN 60529): IP 20
· Overvoltage category (according to IEC 60664-1): III
· Bus: Safety extra-low voltage SELV DC 24 V
· Device complies with EN 50090-2-2
EMC requirements
· Complies with EN 50090-2-2 and EN 61000-6-2
Environmental conditions
· Climatic withstand capability: EN 50090-2-2
· Ambient operating temperature: - 5 ... + 45 °C
· Storage temperature: - 25 ... + 70 °C
· Rel. humidity (not condensing): 5 % to 93 %