The values were measured while sending or receiving successively (at a transmission rate of
1.5 Mbps; bus profile standard; 9 nodes).
Table 1- 2
Request type
PUT
GET
USEND/URCV
BSEND/BRCV
1.4.6

Characteristic data for multiplexing OP connections

General characteristic data
The following information is important when operating HMI (TD/OP) connections:
Characteristic
Number of operable HMI connections
When multiplexing OP connections, the following acyclic services are supported:
• read once
• write once
• read system status list
If cyclic services or ProAgent interfacing (ALARM_S message block) are required, please
continue to use the rack/slot addressing of the remote S7-300 CPU.
Note
PG connections and connections to WinCC
PG connections and connections to WinCC are not operated over the multiplexer. When
operating a PG, a connection resource is always occupied.
CP 342-5
Equipment Manual, 01/2023, C79000-G8976-C146-11
Number of S7 frames per second for CPU 317
Frame length
<=160 bytes
<=160 bytes
<=160 bytes
<=160 bytes
<=400 bytes
<=800 bytes
Application and functions
1.4 Performance data and behavior in operation
Number of S7 frames per
second
29 / s
26 / s
35 / s
25 / s
14 / s
8 / s
Explanation / values
16 max.
17