Figure 1: Configuring An Embedded Profinet Controller - Emerson PACSystems RX3i User Manual

Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

PACSystems™ RX3i and RSTi-EP CPU Reference Manual
GFK-2222AK
If the Embedded PROFINET Controller feature is to be configured, it must be configured
on LAN2 for the CPUs listed above. In the case of RX3i CPE400, CPL410 and RSTi-EP
CPE100/CPE115, which are Rackless CPU's, this will be its only PROFINET Controller. In the
case of CPE330, the Embedded PROFINET Controller can co-exist with any rack-mounted
PROFINET Controllers (IC695PNC001) present in its CPU rack.
To enable the Embedded PROFINET Controller in a project in PAC Machine Edition
select the RX3i CPE400, CPL410, or CPE330, or RSTi-EP CPE100/CPE115 target in the PME
Navigator (Figure 1) and open the Hardware Configuration. On the Settings tab, change
the designated LAN Mode of the selected port to PROFINET. The PROFINET Controller node
description then displays that a PROFINET node exists on the selected LAN.
For further details, refer to the PACSystems RX3i & RSTi-EP PROFINET IO-Controller User
Manual, GFK-2571G or later.

Figure 1: Configuring an Embedded PROFINET Controller

A PROFINET configuration may be transferred between a PROFINET Controller module
(IC695PNC001) and the target Embedded PROFINET IO-Controller using the cut / copy /
paste or equivalent drag and drop functions in PACMachine Edition.
Note: If the PME Project has PROFINET redundant devices, you must record any unique
Secondary Target information and disable Redundancy before cut / copy / paste functions
13
CPE400 firmware version 9.00 or later is required for the embedded PROFINET Controller feature.
14
CPE330 firmware version 8.90 or later is required for the embedded PROFINET Controller feature.
15
PAC Machine Edition™ (PME) 9.50 SIM 4 or later is required in order to configure the MRP parameters for CPE100/CPE115.
16
PAC Machine Edition Logic Developer PLC 8.60 SIM 13 or 9.00 SIM 4 or later is required for configuration of the Embedded PROFINET
Controller function.
CPU Features & Specifications
RX3i CPE400
13
RX3i CPE330
14
RSTi-EP CPE100/CPE115
15
Section 2
October 2019
16
,
18