PACSystems™ RX3i and RSTi-EP CPU Reference Manual
GFK-2222AK
on PROFINET Controller modules will work. Then, re-enable Redundancy, mirror, and
restore your unique Secondary Target information.
The Embedded PROFINET Controller may be configured as a Simplex PROFINET IO-
Controller with support for up to 32 I/O devices. For update rates, loading and other
considerations, refer to the PACSystems RX3i PROFINET IO Controller User Manual,
GFK-2571F or later.
The Embedded PROFINET Controller supports Media Redundancy Protocol (MRP) and
may be used as either a Media Redundancy Manager (MRM) or Media Redundancy Client
(MRC) on a redundant media ring. For details concerning the Media Redundancy
Protocol, refer to the PACSystems RX3i PROFINET IO Controller User Manual, GFK-2571F or
later.
The following CPUs support Hot Standby Redundancy with PROFINET IO, using the
embedded PROFINET Controller (LAN2):
For embedded PROFINET Controllers, this feature permits control of up to 32 devices, 20
of which may be redundant. For rack-mounted IC695PNC001, this feature permits
control of up to 128 devices, all of which may be redundant.
Note that the host PLC CPU can support up to 255 redundant devices, which may be
allocated across 2, 3, or 4 PROFINET Controllers (any combination of embedded
PROFINET Controller and/or PNC001 modules).
2.1.6

OPC UA

Each PACSystems CPE302/CPE305/CPE310/CPE330/CPE400/CPL410 supports Open
Productivity and Connectivity Unified Architecture (OPC UA) Server
the embedded Ethernet port only.
Effective with CPE310/CPE305 firmware version 8.20, or CPE302 firmware version 9.40,
the CPE embedded Ethernet port supports OPC UA Server.
Effective with CPE310/CPE305 firmware version 9.20, or CPE330 firmware version 9.21,
or CPE302 firmware version 9.40, OPC UA Server is configurable through PAC Machine
Edition
For more information on OPC UA support refer to PACSystems RX3i and RSTi-EP TCP/IP
Ethernet Communications User Manual, GFK-2224 version M or higher.
17
Not supported by RSTi-EP CPE100/CPE115 at the time of publication.
18
PAC Machine Edition Logic Developer PLC 9.00 SIM 10, or 9.50 SIM 2, or later is required for OPC UA Server configuration.
CPU Features & Specifications
CPE330 with firmware version 9.40 or later. The PROFINET Controller may be the
embedded PROFINET Controller or a rack-mounted IC695PNC001.
CPE400 with firmware version 9.30 or later. The PROFINET Controller is always the
embedded PROFINET Controller.
CPL410: The PROFINET Controller is always the embedded PROFINET Controller.
.
18
Section 2
October 2019
communications on
17
19