To enable redundancy in a CPE330 project, select the CPE330 target in the PME
Navigator and use the Property Inspector to change the Enable Redundancy target
property to True.
3.4.

PROFINET Controller Configuration

PROFICY Machine Edition 8.60 SIM 13, PME 9.00 SIM 4 or later may be used to
configure an Embedded PROFINET Controller in the CPE330 Hardware Configuration
on LAN 2.
To enable the PROFINET Controller in a CPE330 project, select the CPE330
the PME Navigator and open the Hardware Configuration. On the Settings tab,
change the LAN 2 Mode to PROFINET. The PROFINET Controller node description now
displays that it is using LAN 2 as a submodule under the CPE330.
3.5.
Backward Compatibility with
CPU320/CRU320/CPU315
The CPE330 also serves as a drop-in replacement for the CPU320, CRU320, and
CPU315 Controllers without the need to upgrade PME. To download projects
intended for the CPU320/CRU320 to a CPE330 with versions of PME that do not
support the CPE330, you must change the CPE330's compatibility setting.
To change the compatibility setting, perform the following operations:
1.
Power off the CPE330 and remove any USB stick that might be attached to
its USB connector.
2.
Place the CPE330's RUN/STOP switch in the STOP position.
3
CPE330 release 8.90 or later is required for the embedded PNC feature.
Hardware Installation
Section 3
Sep 2019
3
target in
16