Power Supply Wiring
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury.
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements
for field wiring installation and grounding as
described in NEC and your local/state/national
electrical codes.
Note: Graphic labels (shown above) are used for CE
application only.
66
Important:
X39003892001A
Before servicing, disconnect all power
sources and allow at least 30 minutes for
capacitors to discharge.
All electrical enclosures—unit or remote—
are IP2X.
The IPC wiring shield should be grounded
on one end only at control panel end. The
other end should be un-terminated and
taped back on the cable sheath to prevent
any contact between shield and ground.
Oil Pump Interlock: All starters must
provide an interlock (normally open)
contact with the chiller oil pump connected
to the control panel at terminals 1X1-10
and 1X1-21 (14 AWG; for AWG/MCM
2
equivalents in mm
, refer to the table in
"Electrical Requirements," p.
purpose of this interlock is to maintain the
oil pump signal in the event that a starter
failure, such as welded contacts, keeps
the chiller motor running after the
controller interrupts the run signal.
53). The