Preparations For Vent And Draining Option - Napoleon WSX-EN Series Installation And Operating Instructions Manual

Two stage multi position high efficiency (condensing) forced air gas furnace
Table of Contents

Advertisement

Available languages

Available languages

30
NOTE
Condensate drain tubing must be cut to
IOM
IOM
appropriate length and slopping towards
condensate trap, ensuring that drain hoses
do not create traps prior to the condensate
trap assembly.
Condensate trap must be primed with
water prior to initial furnace start up.
Barbed fi ttings must be fully inserted into
condensate trap.
11.3
EXHAUSTER ROTATION INSTRUCTIONS & PRESSURE SWITCH MOUNTING
IMPORTANT:
THESE FURNACES DO NOT ALLOW FOR EXHAUSTER ROTATION. REFER TO FOLLOW
ILLUSTRATIONS FOR REFERENCE.
1. Loosen collar clamp and pull up exhaust pipe for adequate clearance.
2. Disconnect exhauster wire connection.
3. Remove the 4 exhauster screws.
4. Remove pressure switch assembly (switches) and pressure sensing hoses.
5. Remove exhauster.
6. Reverse the bands on the rubber drain coupling so the screws are accessible if necessary. (Do not
reverse the drain coupling.) Confi rm that directional arrow on drain coupling points away from exhauster.
7. Remove the appropriate plastic cap on the side panel. Install cap on vent opening not in use.
8. Reinstall the exhauster and the pressure switch assembly in the correct orientation with the (4)
exhauster screws removed in step 2. DO NOT USE POWER TOOL. Reinstall the pressure switches so
that they are above the front manifold drain, to eliminate the chance of condensate draining into the
pressure switch sensing hose causing erratic furnace operation. See Figures 16-19 for reference.
9. Rotate the drain coupling so the drain holes are angled downward 15° and tighten coupling band to
exhauster.
10. Complete the venting as installation requires, mounting the exhaust pipe and tightly securing to collar.
Always secure or support the vent and intake to the fl oor joists or rafters to avoid sagging and possible
fatigue of venting materials. This ensures proper drainage and prevents spilling the products of combustion
into the building.
The blower compartment should be completely isolated from the burner compartment, and in tight rooms
with other combustion devices, be completely isolated from the room. Ensure that the combustion door
gasket is in good condition.
IMPORTANT:
KEEP PRESSURE SWITCH HOSES ABOVE FRONT MANIFOLD DRAIN, AND CUT TO
APPROPRIATE LENGTH TO PREVENT ANY SAGS OR TRAPS FORMING IN THE HOSES.
TABLE 5 - EXHAUSTER ORIENTATION
Orientation
Furnace
Upfl ow
Horizontal Right
W415-2845 / B / 11.10.20
Flue
Vertical
Right
Rotate Exhauster (Y/N)
N
N
H16.3.4A
See Figures 16 - 19 for
recommended mounting