NOTE:
Compressor startups are staggered to prevent high electrical circuit
demand.
Once the cases are running, listen for any unusual sounds or events.
Examples include:
Evaporator fan blade interference. Compressors should run
continuously at startup. Use an amperage meter to check the current
to each compressor.
CHECK each fan to ensure it is running. The discharge air output at the
top inside front of the case (honeycomb area) should be relatively even
across the length of the case. VERIFY there are no leaks at connections
for the condenser water.

START UP AND OPERATION

See the merchandiser's Technical Data Sheet for refrigerant settings
and defrost require ments. Bring merchandisers down to the operating
temperatures listed on the data sheet.
Excessive ambient conditions may cause condensation and
therefore sweating of doors. Facility operators should monitor
doors and floor conditions to ensure safety of persons.
HUSSMANN CORPORATION • U.S. & CANADA 1-800-922-1919 • BRIDGETON, MO 63044-2483 • MEXICO 1-800-890-2900 • WWW.HUSSMANN.COM • PN 3053328_H

12 HOURS AFTER START UP CHECKLIST

ANSI Z535.6-2011 (R2017)
Check case temperature.
Page 18
Check if there is any CoreLink alarm.
Check water connections for leaks or accumulation of water.
Providing Information About Safety Messages in Collateral
Verify the fans are running.
Check compressor's amperage, and validate with the information
on serial plate.
Check the door operation again to ensure doors open and close
properly once the case is down to operating temperature.
A1
Explanation of Signal Words and Symbols
Check that all inspection plates and covers have been properly
Signal words and safety symbols that are used in a product's collateral mate
replaced.
be defined in collateral materials if space is available.
Inspect for any water accumulation due to incorrect or unsealed
A1.1
Safety Alert Symbol
penetrations where electrical or other lines pass through
The meaning of the safety alert symbol may be provided in collateral materia
insulated walls of the case.
be used for this purpose.
Verify that the lights are "ON". (lights are switched remotely.)
If lights are "OFF", check the illumination schedule and circuit
breaker for the lights.
Check the water outlet temperature from each condensing unit.
Water outlet temperature should be less than 10° above water
inlet temperature.
A1.2
Signal Words
The meaning of the different signal words as defined by the ANSI Z535.6 an
may be explained in collateral materials. The following artwork may be used
» Due to risk of ignition resulting from incorrect parts or
improper service, only Hussmann authorized personnel may
service this equipment.
» Component parts shall be replaced only with exact
manufacturer and model number components. Failure to
use authorized technicians could result in AN explosion,
death, injury and property damage.
A1.3
Other Highlighting Conventions
The meaning of any other highlighting conventions used to differentiate safe
manipulations, indention, etc.) may be explained in collateral materials.
4-2
A1.4
Safety Symbols
Annex A
Safety Signs and Labels
(Informative)
This is the safety alert symbol. It is
to potential physical injury hazard
messages that follow this symbol
injury or death.
DANGER indicates a hazardous
avoided, will result in death o
WARNING indicates a hazardous
avoided, could result in death
CAUTION indicates a hazardous
avoided, could result in minor
NOTICE is used to address pract
physical injury.
Safety instructions (or equivalent
safety-related instructions or

Advertisement

Table of Contents
loading

This manual is also suitable for:

RmwRlwRltw

Table of Contents