TOP-WIND MODELS
Apply a lightweight oil to the screw stem.

CHECKING GENERATOR DRIVE PLATE TORQUE

Follow the procedure below to check the torque of the generator drive plate bolts in accordance with the maintenance
chart. Refer to
"Basic Maintenance Schedule (John Deere Engine)" on page
1. Disconnect the engine starting battery.
2. Remove the generator fan guard.
3. Torque each of the drive plate bolts to the appropriate specification shown in the table below.
4. Reinstall the generator fan guard. Reconnect the battery.

AUXILIARY FUEL TANK OPTION

The auxiliary fuel tank option is designed so the unit can run from an external
fuel tank. The unit is still programmed to shut down when the internal tank's
fuel level drops below 5%. In order for the unit to run off of an auxiliary tank,
the fuel level in the internal tank must remain over 5%. To operate the unit using
an auxiliary fuel tank, use the following procedure:
1. Shut down the unit and check that the level of fuel in the tank is above 5%.
2. Attach the auxiliary fuel tank's fuel lines to the "AUXILIARY FUEL INLET"
and "AUXILIARY FUEL OUTLET" fittings on the unit.
3. Open the "AUXILIARY FUEL INLET" and "AUXILIARY FUEL OUTLET"
valves located inside of the right front door.
Unit
ft-lb (Nm)
MMG130D
36 (49)
MMG175
46 (63)
MMG205
47 (64)
44.
47