Exhaust Filter Service Requirements; Checking Generator Drive Plate Torque - Generac Power Systems MAGNUM MMG75D Operating Manual

Diesel generator ith power zone controller
Hide thumbs Also See for MAGNUM MMG75D:
Table of Contents

Advertisement

Maintenance
Press  to move the cursor (blue highlighted text) down to the Maintenance group.
4.
Press ► to access the sections. Press  to highlight the Maintenance section.
5.
Press ► to access the parameters and highlight the maintenance alarm that needs to be reset.
6.
Press  to select the editable parameters. The cursor will highlight "Not Reset" under the selected mainte-
7.
nance alarm. Press  to highlight "Reset".
Press  to reset the selected maintenance alarm.
8.
To perform additional maintenance alarm resets, repeat steps 6 - 8.
9.
Note: If the selected maintenance alarm does not need to be reset, press  to highlight "Not Reset" and press 
to return to the parameters section.
To save changes, press and hold  for five seconds. To discard changes made, press and hold O for five
10.
seconds.

EXHAUST FILTER SERVICE REQUIREMENTS

The exhaust filter system contains a Diesel Particulate Filter (DPF). Over time, the DPF will require professional
servicing to remove ash buildup. The expected service interval will be at least 3,000 or 4,500 hours, based on engine
power and operating conditions. Actual service should take place when the indicator light appears on the Power
Zone™ controller. The DPF should be cleaned or replaced by an OEM authorized engine service dealer only. The
removal of DPF ash must be done by removing the DPF from the unit and placing it into specialized equipment.
Do not remove ash by using water or other chemicals. Removing ash by these methods
may cause equipment damage and create unsafe operating conditions.
Only a OEM authorized engine service dealer should remove, handle and dispose of DPF
ash. These materials may be considered hazardous under federal, state and local regula-
To avoid unnecessary buildup of diesel particulates or soot in the exhaust filter system:
1. Utilize the Automatic Exhaust Filter Cleaning mode.
Avoid unnecessary idling.
2.
Use proper engine oil. See the engine operator's manual.
3.
Use only ultra low sulfur diesel fuel. See the engine operator's manual.
4.

CHECKING GENERATOR DRIVE PLATE TORQUE

Follow the procedure below to check the torque of the generator drive plate bolts in accordance with the maintenance
chart.
1. Disconnect battery.
Remove generator fan guard.
2.
40
CAUTION
CAUTION
tions, and must be handled and disposed of properly.
MMG75D-100D Operating Manual
33701 C