08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
10
AD value of current
11
AD value of voltage
12
Indoor unit running mode code
13
Outdoor unit running mode code
14
EXV open angle
15
Frequency limit symbol
16
DC fan motor speed
17
IGBT radiator temp.
Indoor unit number
18
19
Evaporator pipe temp. T2 of 1# indoor unit
20
Evaporator pipe temp. T2 of 2# indoor unit
21
Evaporator pipe temp. T2 of 3# indoor unit
will show "-9".If the temp. is higher than 70 degree, the
digital display tube will show "70". If the indoor unit is not
connected, the digital display tube will show: "――"
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show
"13".If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "0.5",it means the compressor
discharge temp. is 105 degree. the digital display tube show
"1.6",it means the compressor discharge temp. is 116
degree)
The display value is hex number.
Off:0, Fan only 1,Cooling:2, Heating:3
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
Actual data/4.
If the value is higher than 99, the digital display tube will
show single digit and tens digit.
For example, the digital display tube show "2.0",it means the
EXV open angle is 120×4=480p.)
Frequency limit caused by
Bit7
IGBT radiator
Frequency limit caused by
Bit6
PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Frequency limit caused by
Bit1
current
Frequency limit caused by
Bit0
voltage
The display value is between 30~120 degree. If the temp. is
lower than 30 degree, the digital display tube will show
"30".If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "0.5",it means the IGBT radiator
temp. is 105 degree. the digital display tube show "1.6",it
means the IGBT radiator temp. is 116 degree)
The indoor unit can communicate with outdoor unit well.
General:1, Twins:2
If the temp. is lower than 0 degree, the digital display tube
will show "0".If the temp. is higher than 70 degree, the digital
display tube will show "70". If the indoor unit is not
89
The display value is
hex
number.
For
example, the digital
display tube show
2A,
then
Bit5=1,
Bit3=1, Bit1=1.
It means frequency
limit caused by T4,
T3 and current.