16.4.13. J1 Malfunction
Malfunction conditions
Possible causes
J1 displayed
High temperature protection of
condenser
Is the condenser
temperature is Higher than
65°C?
Yes
Is the outdoor ambient
temperature higher than
50 ℃?
No
Is the outdoor unit ventilation
functioning properly?
Yes
Is the outdoor fan running
properly?
Yes
Is the heat exchanger dirty?
No
Replace outdoor main
board. Has the problem
been resolved?
No
If the level of refrigerant is not
sufficient, does the system work after
refrigerant is added?
No
Check whether the refrigerant
system is functioning normally
When the outdoor pipe temperature is more than 65°C, the unit stops. It starts
again only when the outdoor pipe temperature is less than 52°C.
● Faulty condenser temperature sensor
● Dirty heat exchanger
● System leakage or blockages
No
Yes
Stop the unit
Ensure that the outdoor unit
No
ventilate is functioning properly
Refer to the solution to the
malfunction of fan speed being out of
No
control . Find the cause and resolve the
problem.
Yes
Clean the heat exchanger
Is the connection between
temperature sensor and
PCB in working order?
Yes
Is the resistance of
condenser temp. sensor
normal according to
Appendix 1
Yes
109
No
Correct the connection
No
Replace the temperature sensor