Technical Data - Viking FREEDOM VK484 Technical Data Manual

Residential horizontal sidewall sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Model VK484 Sprinkler is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Sprinkler Temperature
Classification
Ordinary
Intermediate
Sprinkler Finishes: Brass, Chrome, White Polyester
The sprinkler temperature rating is stamped on the deflector.
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
2
Refer to specific installation standards.
Sprinklers with ENT, White Polyester, and Black Polyester finishes are C-UL-US-EU Listed as corrosion resistant.
3
The ENT coating has passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
4
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable
for the proposed environment. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with ENT coating.
Figure 1:
Standard Sprinkler Wrench 21475MB
Form No. F_050310
Rev 01
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Nominal
Temperature Rating
155 °F (68 °C)
175 °F (79 °C)
November 2022

TECHNICAL DATA

1
, Black Polyester
, and ENT
3
3
Footnotes
FREEDOM
HORIZONTAL SIDEWALL
SPRINKLER VK484 (K4.2)
Maximum Ambient
Ceiling Temperature
2
100 °F (38 °C)
150 °F (65 °C)
3,4
Page 2 of 5
RESIDENTIAL
®
Bulb Color
Red
Yellow