Download Print this page

Viking FREEDOM VK484 Technical Data Manual page 13

Residential horizontal sidewall sprinkler

Advertisement

Sprinkler RES7
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
SPACING OF RESIDENTIAL SPRINKLERS LISTED FOR USE
BELOW SLOPED CEILINGS UP TO AN 8/12 (33.7°) PITCH
(Refer to the appropriate residential sprinkler technical data page for listings.)
Pendent Sprinklers
(A) One-half listed spacing of sprinkler maximum, 0'-4" (0-102 mm) minimum.
(B) Listed spacing of sprinkler, maximum, 8'-0" (2.4 m) minimum.
(C) Where angle "C" is greater than an 8/12 (33.7°) pitch, see Figure 2 below.
SPACING OF RESIDENTIAL SPRINKLERS BELOW SLOPED
(NOTE: Refer to NFPA 13D or NFPA 13R, and the Authority Having Jurisdiction.)
Form No. F_080190
18.10.25
TECHNICAL DATA
Single Slope
CEILINGS WITH GREATER THAN 8/12 (33.7°) PITCH
(A) One-half listed spacing of sprinkler, maximum.
(B) 3'-0" (.91 m) maximum.
(C) 0'-4" (0-102 mm) minimum.
(D) Slopes greater than an 8/12 (33.7°) pitch.
(E) For distance less than 8'-0" (2.4 m), baffle required.
Rev 16.1.P65
Horizontal Sidewall Sprinklers
(Spray Across the Slope)
Figure 1
Figure 2
FREEDOM
RESIDENTIAL
®
SPRINKLER
INSTALLATION GUIDE
Multiple Slope

Advertisement

loading