2-6 Compaq 3000 Series UPS Operation and Reference Guide
Use this procedure to activate the REPO port:
1. Install a suitable switch at the required remote location.
2. Remove the connector block from the REPO port.
Figure 2-2. Removing the connector block
3. Wire the connector block using stranded, non-shielded wire
(AWG #22 - #18, or equivalent).
4. Replace the connector block in the REPO port.
Figure 2-3. Replacing the connector block
IMPORTANT: The remote switch must be in the OFF (open) position to enable power to
the output receptacles.