Toshiba MMK-UP0051DHPL-E Installation Manual page 38

Indoor unit high-wall type
Hide thumbs Also See for MMK-UP0051DHPL-E:
Table of Contents

Advertisement

5
Push the menu button to make Set data
[
] flash. Change Set data [
with [
] [
] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
• To change other settings of the selected
indoor unit, repeat from Procedure
7
When all the settings have been completed,
push ON/OFF button to determine the
settings.
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
• To change settings of another indoor unit,
repeat from Procedure
37-EN
]
4
.
" is flashing.)
1
.
‒ 37 ‒
Change of lighting time of filter
sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No. in Procedure
• For the [SET DATA] in Procedure
SET DATA of filter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
0001
150H (Factory setting)
0002
0003
0004
To secure better effect of heating
When it is difficult to obtain satisfactory heating
due to installation place of the indoor unit or
structure of the room, the detection temperature of
heating can be raised. Also use a circulator, etc. to
circulate heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
(
• For the CODE No. in Procedure
• For the SET DATA in Procedure
the SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Detection temp shift value
0000
0001
0002
0003
0004
0005
0006
Installation Manual
6
).
4
, specify [01].
5
, select the
None
2500H
5000H
10000H
6
).
4
, specify [06].
5
, select
No shift
+1°C
+2°C (Factory setting)
+3°C
+4°C
+5°C
+6°C