4.2.4 Installing and Connecting the EVS-SW24 to the EVS-VCM
The EVS-SW24 adds 24 switches to the 5820XL-EVS and 6820EVS control panels for a total of 40 (with the 16 non-EVS switches on the
EVS-VCM).
Follow these steps to install and connect the EVS-SW24:
1.
Open the cabinet door and dead front panel.
2.
Remove AC power from the main control panel.
3.
Disconnect the backup batteries.
4.
Install the EVS-SW24 on the six mounting studs located on the inside of the dead front panel. See Figure 4.3 for mounting locations.
5.
Connect one end of the wiring assembly (P/N 130398, supplied) to the EVS-VCM and the other end to the EVS-SW24 as shown in
Figure 4.5.
6.
Secure the switch expander to the dead front panel using the supplied six ¼" hex nuts.
7.
Restore AC power.
8.
Reconnect backup batteries.
4.2.5 Installing the Microphone
To install the microphone follow these steps:
1.
Clip the microphone into the microphone clip.