Removing Transformer T1
Transformer T1 Removal
2.1
Removal should be performed only by qualified personnel.
To remove Transformer T1, perform the procedures in the following paragraphs.
Refer to Chapter 1 Getting Started for tools and equipment required to remove
transformer.
2.1.1
Hardware Removal for Access to T1
To gain access to T1, perform the following procedure:
NOTE: Retain all removed assemblies and hardware, and store in a safe place to
prevent damage. Assemblies and hardware will be reinstalled upon
completion of the removal procedure.
1.
Move the Output/Inverter Cabinet to the work area determined using the
guidelines presented Chapter 1 Getting Started.
2.
Open cabinet doors.
3.
Remove top door hinges and remove doors.
4.
Remove four rear panels from cabinet as follows (see figure 2---1):
a.
Remove panel 1 by loosening four screws at bottom of panel and
removing ten screws from top and sides. Remove panel.
b.
Remove panel 2 by loosening four screws at bottom of panel and
removing ten screws from top and sides. Remove panel.
c.
Remove panel 3 by loosening four screws at bottom of panel and
removing six screws from sides. Remove panel.
d.
Remove panel 4 by loosening four screws at bottom of panel and
removing six screws from sides. Remove panel.
5.
Remove vertical center channel by removing two top and two bottom screws
(see figure 2---2).
6.
Remove rear transformer baffle by removing two screws(see figure 2---2).
7.
Disconnect blower connectors B8P1 through B11P1.
8.
Remove four front screws, and one left and one right side screw securing
blower assembly B8---B11 (see figure 2---3).
Powerware 9315 (500 kVA- -750 kVA) T1 and T3 Installation Addendum
164201244- - 001 REV. A 011500
WARNING:
2
2--1