Installation
2 Stage Thermostat, 1 Stage AHU
AHU Control Unit (ACU)
Thermostat
Input
Y1
Y1
Y2
Y2
G
G
W1
W1
W2
W2
D
D
O/B
O/B
R
C
DIP SW1
1
2
2 Stage Thermostat, 2 Stage AHU
AHU Control Unit (ACU)
Thermostat
Input
Y1
Y1
Y2
Y2
G
G
W1
W1
W2
W2
D
D
O/B
O/B
R
C
DIP SW1
1
2
18 English
AHU + Electric Heat with Heat Pump Configuration (continued)
Indoor unit
Output
Y1
Y
Y2
G
G
W1
W1
W2
W2
D
D
O/B
O/B
R
R
C
C
on
off
3
4
5
6
7
8
AHU + Electric Heat (emergency heat) with Heat Pump Configuration
Indoor unit
Output
Y1
Y1
Y2
Y2
G
G
W1
W1
W2
W2
D
D
O/B
O/B
R
R
C
C
on
off
3
4
5
6
7
8
•
Please review the Option Settings section for
additional system option settings.
•
If an auxiliary heater is installed and the heater
can operate simultaneously with the heat-pump,
configure the thermostat as a 2 stage heat pump
and configure the 4-way reversing valve to B. If a W1
or W2 signal is input, the heat-pump and auxiliary
heater can operate simultaneously.
NOTE
•
•
If the indoor unit only has a Y input terminal, connect
it to the Y1 output terminal in the Indoor section of
the AHU Control Unit (ACU).
•
Connection of the dehumidification (D) terminal is
optional. If the thermostat and the AHU/furnace
supports a dehumidification signal, the outdoor unit
and AHU Control Unit (ACU) will adjust operation to
optimize dehumidification.
•
•
•
Connection of the dehumidification (D) terminal is
optional. If the thermostat and the AHU/furnace
supports a dehumidification signal, the outdoor unit
and AHU Control Unit (ACU) will adjust operation to
optimize dehumidification.