Installing An Spc - Juniper SRX 5800 Installation Instructions Manual

Services gateway
Hide thumbs Also See for SRX 5800:
Table of Contents

Advertisement

SRX 5800 and SRX 5600 Services Gateway Services Processing Card Installation Instructions
Do not stack SPCs on top of one another after removal. Place each one individually
in an electrostatic bag or on its own antistatic mat on a flat, stable surface.
9.
Figure 6: Removing an SPC

Installing an SPC

To install an SPC (see Figure 7 on page 11):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
10
Replacing SPCs
If you are not reinstalling an SPC into the emptied slot within a short time, install
a blank panel over the slot to maintain proper airflow in the card cage.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and
connect the strap to one of the ESD points on the chassis. For more information
about ESD, see "Preventing Electrostatic Discharge Damage" on page 12.
If you have not already done so, power off the device. See "Powering Off the
Services Gateway" on page 8.
Place the SPC on an antistatic mat or remove it from its electrostatic bag.
Identify the slot on the services gateway where it will be installed.
Verify that each fiber-optic transceiver is covered with a rubber safety cap. If it
does not, cover the transceiver with a safety cap.
Orient the SPC so that the faceplate faces you.
Lift the SPC into place and carefully align the sides of the SPC with the guides
inside the card cage.
Slide the SPC all the way into the card cage until you feel resistance.
Grasp both ejector handles and rotate them clockwise simultaneously until the
SPC is fully seated.
If the SPC uses fiber-optic cable, remove the rubber safety cap from each
transceiver and cable.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srx 5600

Table of Contents