SRX 5800 and SRX 5600 Services Gateway Services Processing Card Installation Instructions
If you must insert the card into a bag by yourself, first lay the card horizontally on
a flat, stable surface, sheet metal side down. Orient the card with the faceplate facing
you. Carefully insert the card connector edge into the opening of the bag, and pull
the bag toward you to cover the card.
Never stack a card under or on top of any other component.

Replacing SPCs

SPCs are installed in the front of the services gateway. Before you remove or install
an SPC, you must power off the services gateway (see "Powering Off the Services
Gateway" on page 8). To replace an SPC, use the following procedures:

Powering Off the Services Gateway

Before installing or removing SPCs you must power off the services gateway::
1.
2.
3.

Removing an SPC

An SPC weighs up to 13.1 lb (5.9 kg). Be prepared to accept its full weight.
8
Replacing SPCs
Powering Off the Services Gateway on page 8
Removing an SPC on page 8
Installing an SPC on page 10
On the external management device connected to the Routing Engine, issue the
request system halt
operational mode command. The command shuts down the
Routing Engine cleanly, so its state information is preserved.
user@host> request system halt
Wait until a message appears on the console confirming that the operating system
has halted. For more information about the command, see the JUNOS System
Basics and Services Command Reference.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and
connect the strap to one of the ESD points on the chassis. For more information
about ESD, see "Preventing Electrostatic Discharge Damage" on page 12.
On an AC-powered services gateway, switch the circuit breaker in the chassis
above each power supply to the off position (
gateway, switch the circuit breaker on each power supply faceplate to the off
position (
).
OFF
O
). On a DC-powered services