Bosch Climate 5000 Series Service Manual page 54

Ducted type (medium & high static) air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Service Manual
7.6.2 Indoor / outdoor unit's communication diagnosis and solution (EL 01)
Error Code
Malfunction decision conditions
Supposed causes
Table 23
Troubleshooting:
Power off, then restart the unit after 2
Does the error code
Check the wiring connection
between indoor and outdoor
unit , are they good?
Measure the DC voltage between N/L2
and S (Black pin to N/L2, Red pin to S).
For units with main PCB and IPM board
Check the AC voltage of L, N
output to IPM board, is it same
Unplug all the high voltage
components connected to main
PCB such as 4 way valve, heater,
AC fan one by one to check their
resistance. Is there any component
Check the DC 5V, 12V
from IPM board to main
PCB, are they normal?
Unplug electronic expansion valve.
Check if the DC 5V, 12V to main
Figure 69
5 4 |
EL 01
Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.
Incorrect installation of indoor to outdoor control wire
Electromagnetic interference
Indoor or outdoor PCB faulty
minutes.
Yes
disappear?
No
Correct the connection or
No
change wires
The value is alternative
from negative to positive
Yes
The value is fixed and close
The value is always positive
For units without W
wire
Check the wiring connection
from outdoor terminal to
both
outdoor PCB and wiring
between PCBs if there is
more than 1 PCB
No
Replace main PCB
as power input?
Yes
Yes
short circuit?
Yes
No
No
Yes
PCB are OK
No
Replace IPM board
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump (11.2022)
Solved
Check the wiring connection
from indoor terminal to indoor
to 0
PCB, are they good?
For units
with W wire
Turn on the unit, check if W
and 1(L) is connected?
Yes
For units with only one
PCB
Replace outdoor PCB
Yes
Replace short-circuited
component and main
PCB
Replace short-circuited
component and outdoor
Yes
PCB
No
Replace coil of electronic
Yes
expansion valve
For certain models, outdoor PCB can not be removed
separately. In this case, the outdoor electric control box
should be replaced as a whole.
Repalce indoor PCB
No
Check if the power LED is
on?
No
Unplug all the high voltage
components connected to main
PCB such as 4 way valve, heater,
AC fan one by one to check their
resistance. Is there any component
short circuit?
No
Unplug electronic expansion valve.
Check if power LED is on?