Bosch Climate 5000 Series Service Manual page 40

Ducted type (medium & high static) air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Service Manual
Micro-switch SW2 is for selection of indoor FAN ACTION if room temperature
reaches the set point and the compressor stops.
Range: OFF (in 127s), Keep running
Figure 40
Micro-switch SW3 is for selection of auto-restart function.
Range: Active, inactive
Figure 41
Micro-switch SW5 is for setting mode priority of multi connection.
Range: Heat, cool
Figure 42
4 0 |
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump (11.2022)
Micro-switch SW6 is for selection of temperature compensation in heating mode.
This helps to reduce the real temperature diff erence between ceiling and fl oor so
that the unit could run properly. If the height of installation is lower, a smaller value
could be chosen.
Range: 6 °C, 4 °C, 2 °C, E function (reserved for special customizing)
Figure 43
Micro-switch S1 and dial-switch S2 are for address setting when you want to
control this unit by a central controller.
Range: 00-63
Figure 44