Bosch Climate 5000 Series Service Manual page 32

Ducted type (medium & high static) air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Service Manual
7.3.4 PCB: Regular Single Zone 18K & 24K
BMS500-AAS018-1CSXRC, BMS500-AAS024-1CSXRC
Figure 27
Number
Name
1
Power Supply (CN3)
2
S
3
4-WAY
4
AC-FAN
5
HEAT2
6
T5 T4 T3
7
PMV
8
HEAT1
9
DC-FAN
10
TESTPORT
11
FAN_IPM
12
COMP_IPM
U
13
V
W
14
EE_PORT
Table 18
3 2 |
CN#
Description
CN6
Earth: connect to Ground
CN7
N_in: connect to N-line (208-230V AC input)
CN8
L_in: connect to L-line (208-230V AC input)
CN2
S: connect to indoor unit communication
CN60
connect to 4 way valve, 208-230V AC when is ON.
CN5
connect to AC fan
CN19
connect to chassis heater, 208-230V AC when is ON
CN17
connect to pipe temp. sensor T3, ambient temp. sensor T4, exhaust temp. sensor T5
CN18
connect to Electric Expansion Valve
CN16
connect to compressor heater, 208-230V AC when is ON
CN414
connect to DC fan
CN23
used for testing
IPM501
IPM for DC fan
IPM1
IPM for compressor
CN27
connect to compressor
CN28
0V AC (standby)
CN29
10-200V AC (running)
CN505
EEPROM programmer port
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump (11.2022)