Installation Procedure
Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product
and on this manual.
•
: The factory refrigerant charge of the product.
•
: The additional refrigerant amount charged in the
field.
•
+
: The total refrigerant charge.
Indoor Unit
Unit
, a
, b
+
, c
Refrigerant type
R-32
•
GWP: Global Warming Potential
•
NOTE
a
Factory refrigerant charge of the product: see unit
name plate
b
Additional refrigerant amount charged in the
field(Refer to the above information for the quantity of
refrigerant replenishment.)
c
Total refrigerant charge
d
Refrigerant cylinder and manifold for charging
24 English
Outdoor Unit
2
1
kg
tCO
e
2
GWP value
675
CAUTION
•
The filled-out label must be adhered in the proximity of
the product charging port (e.g. onto the inside of the stop
valve cover).
•
Make sure that the total refrigerant charge does not
exceed (A), the maximum refrigerant charge, which is
calculated in the following formula: Maximum refrigerant
charge (A) = factory refrigerant charge (B) + maximum
additional refrigerant charge due to piping extension (C).
Model
AC071BXAPKG
AC071BXAPNG
AC100BXAPKG
AC100BXAPNG
AC120BXAPNG
AC140BXAPNG
Charging the refrigerant under conditions of
liquid by using a liquid pipe
It is necessary for recharging under conditions of liquid. When
recharging refrigerant from the refrigerant cylinder to the
equipment, follow the instructions below.
•
Before recharging, check whether the cylinder has
a siphon or not. There are two ways to recharge the
refrigerant.
Cylinder with siphon
siphon
Charge the refrigerant standing
the cylinder upright.
NOTE
•
During the measuring operation of refrigerant quantity
added use an electronic balance. If cylinder doesn't
have syphon, upset it.
(Unit : g)
A
B
C
3825
2700
1125
5975
3500
2475
Cylinder without siphon
Charge the refrigerant turning
the cylinder upside down.