Samsung AC BXAP G Series Installation Manual page 14

Table of Contents

Advertisement

Installation Procedure
3- phase
Model
Indoor unit
Outdoor unit
AC071BN4PKG/EU
AC071BN6PKG/EU
AC071BNMPKG/EU
AC071BXAPNG/EU
AC071BNAPKG/EU
AC071BNCPKG/EU
AC100BN4PKG/EU
AC100BN6PKG/EU
AC100BXAPNG/EU
AC100BNMPKG/EU
AC100BNTPKG/EU
AC120BN4PKG/EU
AC120BN6PKG/EU
AC120BXAPNG/EU
AC120BNMPKG/EU
AC140BN4PKG/EU
AC140BN6PKG/EU
AC140BXAPNG/EU
AC140BNMPKG/EU
NOTE
1
Voltage range
Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
2
Maximum allowable voltage variation between phases
is 2%.
3
Wire size & type must comply with the applicable local
and national code.
Wire size: Based on the value of MCA.
Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more.
4
MFA is used to select the circuit breaker and the ground
fault circuit interrupter (earth leakage circuit breaker).
5
MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
14 English
Outdoor unit
Voltage range (V)
Hz
Rated
Min.
Max.
50 380 to 415
342
456.5
Input current (A)
Outdoor unit
Indoor unit
Cooling
Heating
16.1
16.1
1.5
16.1
16.1
1.5
16.1
16.1
2.5
16.1
16.1
1.0
16.1
16.1
2.5
16.1
16.1
1.5
16.1
16.1
1.5
16.1
16.1
2.5
16.1
16.1
1.0
16.1
16.1
1.5
16.1
16.1
1.5
16.1
16.1
2.5
16.1
16.1
1.5
16.1
16.1
1.5
16.1
16.1
2.5
6
This equipment complies with IEC 61000-3-12 provided
that the short-circuit power S is greater than or equal
to S (*2) at the interface point between the user's
supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a short-circuit power S greater than or equal
to S (*2).
Model
AC071BXAPNG/EU
AC100BXAPNG/EU
AC120BXAPNG/EU
AC140BXAPNG/EU
Power supply
Total
MCA(A)
MFA(A)
17.6
17.6
17.6
17.6
17.6
17.6
18.6
18.6
18.6
17.1
17.1
17.1
18.6
18.6
18.6
17.6
17.6
17.6
17.6
17.6
17.6
18.6
18.6
18.6
17.1
17.1
17.1
17.6
17.6
17.6
17.6
17.6
17.6
18.6
18.6
18.6
17.6
17.6
17.6
17.6
17.6
17.6
18.6
18.6
18.6
S
[MVA]
sc
1.4
1.6

Hide quick links:

Advertisement

Table of Contents
loading