Preventative Maintenance - Culligan 60K Installation, Operation, And Service Instructions With Parts Lists

Top mount (ctm) water softeners models from 2020
Table of Contents

Advertisement

Preventative Maintenance

Suggested Preventive Maintenance Inspection Schedule
The Culligan CTM commercial water softener has been designed to provide a good, consistent service life.
Routinely inspecting the system may help avoid potentially costly breakdowns related to circumstances
outside of the control of the dealer and/or user.
Component
Suggested Inspection Frequency
Entire System
At Startup, after infrequent use (idle for one
week or more) or every 3–6 months if on a
private water supply.
Drain Line
Every 12 months or every time service
Flow Control
is performed on the system.
Control Valve
Every 6–12 months or every time service
is performed on the system.
Softening Media
Every 2–3 years
Pilot Strainer
Every 6-12 months or every time service
is performed on the system.
Softening Cartridge,
Every 6-12 months or every time service
if equipped
is performed on the system.
50
Culligan® Top Mount (CTM) Water Softeners
Table 9.
Reason for Maintenance
On private supplies, the appearance of
off-tastes and odors, particularly if musty
or "rotten egg" (caused by harmless
sulfate-reducing bacteria) may indicate
a need for the system to be sanitized.
Build up of sediment, iron and/or
other foreign materials (found in
some water supplies but not
necessarily all) could negatively
affect system performance. Monitor
item for normal (or unexpected) wear.
Build up of sediment, iron and/or
other foreign materials (found in
some water supplies but not
necessarily all) could negatively
affect system performance. Monitor
item for normal (or unexpected) wear.
Chlorinated water supplies can break-
down/destroy resin material. Resin material
may also perform poorly if subjected to
other materials (sediment, iron, alum, etc)
found in some water supplies (but not
necessarily all).
Build up of sediment, iron and/or
other foreign materials (found in
some water supplies but not
necessarily all) could negatively
affect system performance. Monitor
item for normal (or unexpected) wear.
Exhausted cartridge.
Build up of sediment, iron and/or
other foreign materials (found in
some water supplies but not
necessarily all) could negatively
affect system performance. Monitor
item for normal (or unexpected) wear.
50
Cat. No. 01029401

Advertisement

Table of Contents
loading

This manual is also suitable for:

90k120k150k210k300k450k ... Show all

Table of Contents