Rinnai EHPS215VM Operation & Installation Manual page 25

Heat pump hot water system
Table of Contents

Advertisement

water will be heated up to 70°C and thereafter maintained at 65°C~70°C. After 30 minutes it will exit disinfection. If
the water can not reach at 70°C, the heat pump will run in disinfection mode for 2 hours then exit the disinfection.
If the water temperature setting is ≥ 70°C, then disinfection will not be commenced.
Auto Disinfection:
If the water temperature setting is < 70°C cumulatively over a 7 day period, the heat pump will start Disinfection
automatically. After completion, it will re-clock. During Disinfection, the symbol "
light up and the water will be heated up to 70°C and thereafter maintained at 65°C~70°C. After 30 minutes it will
exit disinfection. If the water can not reach at 70°C, the heat pump will run in disinfection mode for 2 hours then
exit the disinfection.
If the water temperature setting is ≥ 70°C, then disinfection will not be commenced.
10. Open Parameter Query
With the power on, press the " " or " " button for 3 seconds, to enter the status query interface. Press the " " or
" " button to query each status. Press the "
No.
Name
00
Fluorine Cycle/Water Cycle system
01
High pressure switch
02
Low pressure switch
03
Water flow switch
04
EEV open
05
Coil temp.
06
Ambient temp.
07
Suction temp.
08
Exhaust temp.
09
Water inlet temp.(Water tank)
10
Water outlet temp.
11
Compressor
12
4 way valve
13
High fan speed
14
Low fan speed
15
Circulation pump
16
Heating element
17
Compressor working time before defrosting
18
Link switch
19
Program code
20
Dial switch
21
Dial switch
22
Phase detecting value
Rinnai
" button to exit status query interface.
Note
0=Water Cycle; 1=Fluorine Cycle
0=Open; 1=Close
0=Open; 1=Close
0=Open; 1=Close
Measured value
Measured value
Measured value
Measured value
Measured value
Measured value
0=OFF; 1=ON
0=OFF; 1=ON
0=OFF; 1=ON
0=OFF; 1=ON
0=OFF; 1=ON
0=OFF; 1=ON
0=OFF; 1=ON
Measured value
0=Open; 1=Close
Show the code
0=Open; 1=Close
0=Open; 1=Close
0=OK; 3=Lack phase;
4=Phase fault; 5=No connection
25
OPERATION
" will flash for 2 seconds then
EHPS Heat Pump OIM - Issue 1