Dell PowerEdge R760 Installation And Service Manual page 39

Table of Contents

Advertisement

Table 24. Continuous Operation Specifications for ASHRAE A4
Temperature
Allowable continuous operations
Temperature range for
altitudes <= 900 m (<=
2953 ft)
Humidity percent range
(non-condensing at all
times)
Operational altitude de-
rating
Table 25. Common Environmental Specifications for ASHRAE A2, A3 and A4
Temperature
Allowable continuous operations
Maximum temperature gradient (applies to both
operation and non-operation)
Non-operational temperature limits
Non-operational humidity limits
Maximum non-operational altitude
Maximum operational altitude
Table 26. Maximum vibration specifications
Maximum vibration
Operating
Storage
Table 27. Maximum shock pulse specifications
Maximum shock pulse
Operating
Storage
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Specifications
5–45°C (41–113°F) with no direct sunlight on the equipment
Excursion Limited Operation
8% RH with -12°C (10.4°F) minimum dew point to 90% RH with 24°C (75.2°F) maximum dew
point
Maximum temperature is reduced by 1°C/125 m (1.8°F/410 Ft) above 900 m (2953 Ft)
Specifications
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (9°F in 15
minutes), 5°C in an hour* (9°F in an hour) for tape hardware
NOTE:
not instantaneous rates of temperature change.
-40 to 65°C (-40 to 149°F)
5% to 95% RH with 27°C (80.6°F) maximum dew point
12,000 meters (39,370 feet)
3,050 meters (10,006 feet)
Specifications
0.21 G
1.88 G
Specifications
Six consecutively executed shock pulses in the positive and negative x, y,
and z axis of 6 G for up to 11 ms
Six consecutively executed shock pulses in the positive and negative x, y,
and z axis (one pulse on each side of the system) of 71 G for up to 2 ms
5-35°C (41-95°F) Continuous Operation
35-40°C (95-104°F) 10% Annual Runtime
40-45°C (104-113°F) 1% Annual Runtime
* - Per ASHRAE thermal guidelines for tape hardware, these are
at 5 Hz to 500 Hz for 10 minutes (all operation orientations)
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
rms
Technical specifications
39