Pressure Sensor(High/Low Pressure Sensor); Outdoor Fan - LG Multi V Water IV ARNU07GTU 2 Series Service Manual

Hide thumbs Also See for Multi V Water IV ARNU07GTU 2 Series:
Table of Contents

Advertisement

Checking Method for Key Components

2.5 Pressure Sensor(High/Low Pressure Sensor)

Connect manifold gauge to the service valve of outdoor unit, and compare the output of high pressure sensor to
the output of low pressure sensor to detect the defect.
below) Compare the output of pressure sensor to the output of manifold gauge pressure using the table below.
Read the pressure clearly between black and white as the composition of pressure sensor.
<Low Pressure Sensor>
OUTPUT CHARACTERISTICS
1) If the pressure of manifold gauge is 0~1kg/cm
ant. Find the place of leakage and fix it.
2) If the difference of the outputs of high and low pressure is in the range of 1kg/cm
3) If the difference of the outputs of high and low pressure is over 1kg/cm
need to be replaced.
4) The composition of pressure sensor
Pressure
sensor
The pressure sensor is composed like the circuit picture shown above. If DC 5V voltage flows on red and black
wire, voltage would be made between the white and black wire. The pressure which is equivalent to the pressure
output is shown in the table above.

2.6 Outdoor Fan

1) The outdoor fan is controlled by the inverter motor which can control the number of rotations.
2) The outdoor fan is controlled by the high/low pressure of the outdoor unit after the operation of compressor.
3) There is possibility that the outdoor fan does not operate due to low capacity operation or low outdoor tempera-
ture even if the compressor is operating. This does not mean breakdown of the unit, the fan will start operating if
it reaches the set point.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
2
, it indicates the pressure got lower due to the leakage of refriger-
High Pressure Sensor : 0~5MPa
Vout 0.5~3.5V
Low Pressure Sensor : 0~2MPa
Vout 0.5~3.5V
(Red)
±5%
(White)
(Black)
<High Pressure Sensor>
OUTPUT CHARACTERISTICS
2
, the pressure sensor is out of order, it
- 52 -
, the pressure sensor is normal.
2
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v water iv arnu09gtu 2 seriesMulti v water iv arnu12gtu 2 seriesMulti v water iv arnu18gtt 2 seriesMulti v water iv arnu24gtt 2 seriesMulti v water iv arnu05gtr 2 seriesMulti v water iv arnu07gtr 2 series ... Show all

Table of Contents