Internal Use Only
http://biz.lgservice.com
Outside Unit
R410A
SERVICE MANUAL
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.

Advertisement

Table of Contents
loading

Summary of Contents for LG Multi V Water IV ARNU07GTU 2 Series

  • Page 1 Internal Use Only http://biz.lgservice.com Outside Unit R410A SERVICE MANUAL CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
  • Page 2: Table Of Contents

    Part 2 Outside Units ....................15 Part 3 PCB Setting and Test Run ................38 Part 4 Trouble shooting guide................43 - 2 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3: Safety Precautions

    • There is risk of fire, electric shock, explosion, or • There is risk of fire, electric shock, explosion, or injury. injury. - 3 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4 Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result - 4 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 • To avoid vibration or water leakage. • If the gas leaks and accumulates around the unit, an explosion may result. - 5 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 • If the base collapses, the air conditioner could erate heat and cause a fire. fall with it, causing property damage, product failure, or personal injury. - 6 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7 • Be careful and avoid personal injury. • There are sharp and moving parts that could cause personal injury. - 7 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8: Part 1 General Information

    2.1 Indoor Unit .............11 2.2 Outside Unit............12 3. Combination of Outside Units........13 4. Nomenclature..............14 4.1 Indoor Unit .............14 4.2 Outside Unit............14 - 8 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9: Model Names

    ❈ *ART COOL- SE/S8( * R:Mirror, V:Silver), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma - 9 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10: Outside Unit

    3 Ph, 380-415 V, 50 Hz 720LAS4 740LAS4 760LAS4 780LAS4 800LAS4 3 Ph, 380 V, 60 Hz Heat Pump ARWN - 10 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11: External Appearance

    * A:Basic, C:Plasma ❈ In matters of combination with Outdoor unit system, refer the PDB of that outdoor units. - 11 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12: Outside Unit

    ARWN440LAS4 ARWN460LAS4 ARWN480LAS4 ARWN500LAS4 ARWN520LAS4 ARWN540LAS4 ARWN560LAS4 ARWN580LAS4 ARWN600LAS4 ARWN620LAS4 ARWN640LAS4 ARWN660LAS4 ARWN680LAS4 ARWN700LAS4 ARWN720LAS4 ARWN740LAS4 ARWN760LAS4 ARWN780LAS4 ARWN800LAS4 - 12 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13: Combination Of Outside Units

    ARWN440LAS4 ARWN460LAS4 ARWN480LAS4 ARWN500LAS4 ARWN520LAS4 ARWN540LAS4 ARWN560LAS4 ARWN580LAS4 ARWN600LAS4 ARWN620LAS4 ARWN640LAS4 ARWN660LAS4 ARWN680LAS4 ARWN700LAS4 ARWN720LAS4 ARWN740LAS4 ARWN760LAS4 ARWN780LAS4 ARWN800LAS4 - 13 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14: Nomenclature

    Cooling Only or Heat Pump N: Inverter and H/P Indicates that this is Water System Outside Unit using the R410A - 14 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15: Part 2 Outside Units

    Part 2 Outside Units - 15 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16 4.8 Vacum mode ......................34 4.9 Forced oil return ......................35 4.10 Refrigerant noise reduction mode ................36 4.11 Cycle Data View .......................37 - 16 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17: Basic Control

    Comp 1 Comp 1 Cooling and heating load Fuzzy Control Inverter linear control as cooling and heating load increasing - 17 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18: Master And Slave Unit's Eev Control

    - Td ≤ 80℃ : VI_SH = 3℃ - 80℃<Td ≤ 90℃ : VI_SH = -2*Td/10 + 19 - 90℃<Td : VI_SH = 1℃ - 18 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19: Special Control

    ■ Starting condition : When low oil level which is measured by oil level sensor is kept continuously then oil return operation will be start. ■ Oil return process ends if compressor protection control starts - 19 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20 ■ Oil return operation time : 3 min for running step ■ Starting condition:same as cooling mode ■ Oil return process ends if compressor protection control starts - 20 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21: Stop Operation

    When oil level which is measured by oil level sensor is kept differently between each compressor then oil equalizing EEV will be open during 5 minutes. - 21 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22: Protection Control

    ≥ 190 kPa Normal control ❈ Frequency holding : frequency (or RPM) is not increasing ( can decrease ). - 22 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23: Discharge Temperature Control

    41A or more ❈ AC input current is input current of inverter compressor except constant current (current pass through noise filter) - 23 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24: Phase Detection

    - The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch the connecting terminal with hand nor short two wires directly. - 24 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25: Other Control

    Total capacity including sub units is displayed (2sec) Heat pump : Display 2 is default value Power type Model type - 25 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26 Every indoor unit displays its address on wired remote controller and the 7 segment of main PCB is off. - 26 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27 * Functions save in EEPROM will be kept continuously, though the system power was reset. - 27 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28: Cool & Heat Selector

    • If do not use a function, set an off-mode. • If use a function, first install a Cool & Heat selector. - 28 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29: Geothermal Mode

    Anti freeze type CAUTION • Ask an authorized technician to setting a function. • Anti freeze is essential for geothermal mode. - 29 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30: 220 V Out For Solenoid Valve

    • Ask an authorized technician to setting a function. • If do not use a function, set an off mode. - 30 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31: Variable Water Flow Control

    • Ask an authorized technician to setting a function. • If do not use a function, set an off mode. - 31 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32: Outside Unit Adress

    • If do not use a function, set an off mode. • It is recommended using a sump heater when ambient temperature of outside unit is below 0℃. - 32 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33: Using A Sump Heater

    “oN”~“oFF” Push the ‘●’ button Using a sump heater CAUTION • Ask an authorized technician to setting a function. - 33 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34: Vacum Mode

    Push the reset button on Master unit PCB CAUTION • ODU operation stops during vacuum mode. Compressor can't operate. - 34 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35: Forced Oil Return

    Starting oil return with display “OI” · Auto reset after oil return completed. CAUTION • Ask an authorized technician to setting a function. - 35 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36: Refrigerant Noise Reduction Mode

    Normal mode (Fast cooling & Fast heating) : Off Save the selected option value in EEROM CAUTION • Ask an authorized technician to setting a function. - 36 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37: Cycle Data View

    1 PLS5 1350 op24 vi eev 2 PLS6 op25 IDU running capacity IDU1 op26 Total number of IDU IDU2 - 37 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38: Part 3 Pcb Setting And Test Run

    Part 3 PCB Setting and Test Run - 38 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39 • In case that the outdoor temperature is low, be sure to supply power 4 hours before operation so that the heater is heated(insufficient heating may cause damage of the compressor.) - 39 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40 • When CH05/53/11 ERROR occurs, check if auto-addressing has done and communication wiring is ok. - 40 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41 7 - Segment SW04C (X : cancel) SW03C ( : forward) SW02C ( : backward) SW01C ( : confirm) SW01D (reset) - 41 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42 • Master Unit • Slave Unit Dip switch setting Dip switch setting ODU Setting Slave 1 Slave 2 Slave 3 - 42 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43: Part 4 Trouble Shooting Guide

    Part 4 Trouble shooting guide - 43 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44 2.6 Outdoor Fan .....................52 2.7 Solenoid Valve ..................53 2.8 Reverse Valve...................54 2.9 Temperature Sensor ................54 2.10 Others .....................55 3. Self-diagnosis function ..............56 - 44 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45: The Phenomena From Main Component Failure

    • When CH05/53/11 ERROR occurs, check if auto-addressing has done and communication wiring is ok. - 45 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46: Checking Method For Key Components

    (when measuring absolute values). Accurate measuring values cannot be obtained with a gen- eral movable tester (For analog and digital mode). - 46 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47: Electronic Expansion Valve

    Full open EEV noise. open 1950 pulses - If liquid refrigerant is in EEV, the noise is lower. pulse - 47 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48 - When the coil part is removed or assembled, be careful not to bend the pipe of the body. Body Body - 48 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49 If estimated temperature is very low in comparison with suction temperature which is displayed at remote controller then the valve is not fully closed - 49 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50: Phase Bridge Diode Checking Method

    Otherwise, there is chance of getting electric shock. • There is chance of electric shock by charged voltage. - 50 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 51: Inverter Ipm/Igbt Checking Method

    3.0K Ω ± 10%(25℃) 2.3K Ω ± 10%(25℃) ✽ Red(+) and black(-) are the measuring terminals of multi tester. - 51 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 52: Pressure Sensor(High/Low Pressure Sensor)

    This does not mean breakdown of the unit, the fan will start operating if it reaches the set point. - 52 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 53: Solenoid Valve

    5. Insulation resistance in the state of connecting the valve to coil should be over 100mΩ when measure it with DC mega tester(DC 500V). - 53 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 54: Reverse Valve

    2. Check whether the connector contact of temperature sensor is normal. 3. Measure the resistance of temperature sensor. 10KΩ±1%(25℃) 5KΩ±1%(25℃) 200KΩ±1%(25℃) Resistance 1.07KΩ±3.3%(85℃) 535Ω±3.3%(85℃) 28KΩ±7.7%(85℃) - 54 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 55: Others

    3) Set the multi meter to resistance mode, confirm that the resistance value of the resistor is around 270 kOhm Check and replace inferior components - 55 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 56: Self-Diagnosis Function

    Slave2 outside Unit Inverter Board Input Over Current(RMS) of Slave3 Outside Unit Inverter Board Input Current excess (RMS) Slave3 outside Unit - 56 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 57 Slave3 outside unit inverter DC link over- Compressor turned Off due to Slave3 outside unit inverter DC voltage error voltage over-charge - 57 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 58 Slave3 Outside Unit Low Compression Ratio Slave3 Outside Unit stayed under low Compression limit for 3 Limited minutes - 58 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 59 Slave2 Outside Unit High Pressure Sensor open or short Fault Slave3 Outdoor Unit High Pressure Sensor Slave3 Outside Unit High Pressure Sensor open or short Fault - 59 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 60 When the indoor unit control signal is not received from the 5 3 1 unit controller and indoor unit master Outside unit controller - 60 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 61 Slave2 Outdoor Unit PFC CT Sensor open or short Unit PFC CT Sensor Error of Slave3 Outdoor Slave3 Outdoor Unit PFC CT Sensor open or short Unit - 61 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 62 Slave3 Outdoor Unit Subcooling Outlet Slave3 Outdoor Unit Subcooling Outlet Temperature Sensor Temperature Sensor Error open or short - 62 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 63 Communication error between main MICOM and sub MICOM Communication error between MICOMs Communication error between main MICOM and sub MICOM - 63 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 64 CN-PIPE IN : Pipe inlet temp sensor CN-PIPE OUT : Pipe outlet temp sensor Measure the resistance of outlet pipe temp sensor. - 64 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 65 ❇ The PCB can differ from model to model. Check from the right source. Checking communication cable connection status - 65 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 66 * If the float goes up higher than a half of float switch then the circuit is open & the unit is stopped automatically. (High position Open) float Condensate water - 66 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 67 (Check input of 220V) (Marked as CN-DPUMP) Float switch Housing (CN-FLOAT) [***] Standard of drain pipe head height / slope MAX 450 - 67 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 68 (-9V~+9V) then of communication terminal between IDU and ODU communication from outdoor unit is normal - 68 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 69 - Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control - 69 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 70 (Notice: The connection of motor connector to PCB should be done under no power supplying to PCB) - 70 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 71 After ODU main PCB Replace indoor unit 485 After Auto addressing, reset, error code transmission PCB error code disappears? disappears? - 71 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 72 Check Comp PCB assembly IPM normality. Is Comp PCB assembly → Replace Comp PCB assembly normal? if abnormality found. Recheck power and installation condition - 72 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 73 * Compressor wire connector connection each terminal of compressor point * IPM joining point Check joining conditon Check DC_Link Connector joining condition - 73 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 74 Check Comp PCB assembly IPM normality Is Comp PCB assembly → Replace Comp PCB assembly normal? Recheck power and installation condition - 74 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 75 * Measuring input voltage each terminal of compressor * Compressor wire connector connection * Check DC_Link Connector joining condition - 75 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 76 Check Comp PCB assembly IPM normality. Is Comp PCB assembly → Replace Comp PCB assembly if abnormality found. normal? Recheck power and installation condition - 76 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 77 Troubleshooting Guide * Check DC_Link Connector joining condition N terminal P terminal DC_Link Connector * Measuring input voltage - 77 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 78 LGMV similar as Replace high pressure sensor at manifold gauge? Check pipe is blocked or not and take measure - 78 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 79 → Reassemble if abnormality found Replace Comp PCB assembly. Comp PCB LED display error Recheck power and installation condition - 79 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 80 Check Comp PCB assembly IPM normality Is Comp PCB assembly normal? → Replace Comp PCB assembly Recheck power and installation condition - 80 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 81 Troubleshooting Guide * Measuring resistance between each terminal of compressor * Compressor wire connection - 81 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 82 * Measuring input voltage * Noise filter wiring CN_INV_T CN_INV_S CN_INV_R CN1_SMPS_POWER CN_INV_N CN_DCLINK_P CN_EXT_POWER CN_INV_R CN_INV_S CN_INV_T CN_INV_N - 82 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 83 Check Comp PCB assembly IPM normality Is Comp PCB assembly normal? → Replace Comp PCB assembly Recheck power and installation condition - 83 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 84 Troubleshooting Guide * Measuring resistance between each terminal of compressor * Measuring input voltage * Compressor wire connection - 84 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 85 Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ - 85 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 86 PCB normal? Is the oil sensor Check and correct connection connection on comp normal? Replace oil sensor - 86 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 87 External Communication LED External Communication Connector Communication Connector & Communication Connector & LED in Main PCB LED in External PCB - 87 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 88 If the same error is occurred in mode, is the same error near future replace 4way valve occurred again? Replace 4 way valve***** - 88 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 89 ➃ If there is a unit in which the difference is not increased then the 4way valve of that unit is defective - 89 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 90 Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ - 90 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 91 Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ - 91 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 92 ■ Error diagnosis and countermeasure flow chart Communication Between Push the RESET Replay On-boarding Replace External PCB Main-Sub Micom button LED (Yellow) Blinking - 92 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 93 LED (Yellow) Blinking Press the Rest Button Replay Replace External PCB On-boarding Reset Button Communication LED Between Main and Sub Micom - 93 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 94 1. Set the slave mode with Simple central controller after reset. controller setting normal? Recheck power and installation condition <RS-485 communication wire miss connection> - 94 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 95 November, 2013 P/NO : MFL67103704...