Final Installation Procedures; Triple Leak / Pressure Test - LG LGRED LH188HHV1 Installation Manual

Single-zone convertible mid-static ducted lgred system
Table of Contents

Advertisement

FINAL INSTALLATION PROCEDURES

Triple Leak / Pressure Test

Triple Leak / Pressure Test
After the refrigerant piping installation is complete, perform a triple leak / pressure test. Triple leak / pressure test is performed between the
outdoor unit and indoor unit to verify that refrigerant can flow through the system without danger of leaks or pressure losses. Air and moisture
that is left in the piping can lead to undesirable results and can cause damage to the system. It is important to go through a complete leak /
pressure cycle to be sure that the refrigerant piping is cleared out. This process will have to be repeated if any air or moisture be is found to
remain in the piping.
• Pressure in the system can rise.
• Operating current can rise.
• Inefficient cooling or heating mode capability.
DANGER
nitrogen) when checking leaks, cleaning, installing/repairing pipes, etc. The use of a 800 psig nitrogen regulator is required for safety.
Never perform the leak test using refrigerant.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom (used in a verti-
cal standing position) when the system is pressurized.
• Use only a leak-free gauge manifold set.
• Piping system must not be pressured to more than 550 psi. Pressures greater than 550 psi will damage the piping system and cause unit
malfunction.
Triple Leak / Pressure Check Procedure
1. After the refrigerant piping installation is complete, open the isolation ball valves, if any,
that may have been included in the piping system.
2. Verify that both the liquid and gas (vapor) suction line outdoor unit service ports are
closed, and the stem head access caps are tight. The leak / pressure check is to be per-
formed only to the refrigerant piping system and the connected indoor unit.
3. Remove the cap on the gas (vapor) suction line Schrader port. Connect the (medi-
cal-grade dry) nitrogen cylinder regulator to a gauge manifold, then connect the gauge
manifold to the gas (vapor) suction Schrader port on the service port.
4. Perform the leak / pressure check at 150 psig for fifteen (15) minutes (standing pressure
check).
5. Perform the leak / pressure check at 300 psig for thirty (30) minutes (standing pressure
check).
6. Perform the leak / pressure check at 550 psig for one (1) hour to make sure the piping
system is leak-free. After the gauge reading reaches 550 psig, isolate the system by first
closing the gauge manifold, then close the nitrogen cylinder valve. Check the flared (and
any brazed connections) for leaks by applying a bubble solution to all joints.
The bubble solution must be a solution designed for refrigerant leak testing. Common soap solu-
tion must
never be used on refrigerant piping as those contain chemicals that could corrode
copper and brass, and cause product malfunction.
58
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
• Moisture in the refrigerant circuit will freeze and block capillary
tubing.
• Water can lead to corrosion of parts in the system.
Figure 81: Example of Outdoor Unit Service
Valves. (Appearances Will Vary Depending on
Model.)
Figure 82: Example of a Triple Leak / Pressure
Test Diagram. (Appearances Will Vary Depend-
ing on Model.)
Indoor Unit
Outdoor Unit
Liquid Piping
(Smaller Diameter)
Vapor Piping
(Larger Diameter)
Gauge Manifold
Refrigerant
Piping
Micron
Charge Hose
Gauge
Nitrogen Gas
Tank (Upright
Position)
Connected to Shrader Valve
on Gas (Vapor) Service Port

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lgred lh248hhv1

Table of Contents