Technical data
Positioner data
Note: The following diagram is valid for valves with a standard assignment of the spindle position to the valve position (see
"Mechanical data", page 8).
Control diagram:
Positioner information:
Interface:
GEMÜ 1441
Default setting / The control characteristic is adjustable.
100
75
50
25
0
4
8
During initialization, the 1441 cPos-X positioner automatically detects the control function of the
valve and is adjusted by default so that the valve is closed when the signal is 4 mA*.
The assignment can subsequently be changed using parameters. The close-tight function that is in-
tegrated as standard ensures that the valve is moved completely to the end position when the sig-
nal Open or Close valve is given.
* For double acting actuators, depends on the pneumatic actuator
Control error:
(Dead zone)
Parameterization:
Initialization:
Close tight function:
Function
Parameterization, configuring,
diagnostics
Device status via app
Prerequisite
Compatible smartphone/tablet with
Android or iOS
•
Apple iOS: Version 11 or higher
•
Android: Version 7.0
("Nougat") or higher
•
Bluetooth 4.0 LE or newer
1)
The compatible GEMÜ app can be downloaded in the respective stores (Apple App Store or
Google Play Store).
12
16
20
1% default setting
0.1–25.0% (can be set at fixed values)
0.1–25.0% (adaptive self-adjustment)
Via app or HART
Automatic via magnetic switch, app, digital input
or HART
Closed: W ≤ 0.5% Open: W ≥ 99.5% (can be
changed via the app)
Bluetooth Low Energy
1)
1)
10 / 19
mA
HART
Parameterization, configuring,
diagnostics
Protocol Version 7
Device status via EDD