Appendix
No.
Error Code
Heating operation restricted at outdoor temperature
23
E440
over Theat_high value (default:30°C)
Cooling operation restricted at outdoor temperature
24
E441
below Tcool_low value (default:0°C)
25
E458
Fan speed error
26
E461
Error due to operation failure of inverter compressor
27
E462
System stop due to full current control
28
E463
Over current trip / PFC over current error
29
E464
IPM Over Current(O.C)
30
E465
Comp. Over load error
31
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
32
E467
unconnected wire of compressor
33
E468
Error on current sensor (Short or Open)
34
E469
Error on DC-Link voltage sensor (Short or Open)
35
E470
Outdoor unit EEPROM Read/Write error (Option)
36
E471
Outdoor unit EEPROM Read/Write error (H/W)
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
37
E474
38
E475
Error on inverter fan 2
39
E483
Inverter input voltage sensor error
40
E484
PFC Overload (Over current) Error
Error on input current sensor of inverter 1
41
E485
(Short or Open)
42
E488
Inverter input voltage sensor error
43
E500
IPM over heat error on inverter 1
44
E508
Smart install is not installed
45
E554
Gas leak detected
46
E556
Error due to mismatching capacity of indoor and outdoor unit Check the indoor and outdoor unit capacity
47
E563
Error due to mismatching indoor and outdoor unit
48
E557
DPM remote controller option error
49
E590
Inverter EEPROM Checksum error
54
English
DB68-09343A-00_IBIM_PAC 미라지 이집트파키스탄_IQ_EN.indd 54
Meaning
Remarks
1. Check the range of temperature limited for heating
operation
2. Check the outdoor temperature sensor
1. Check the range of temperature limited for cooling
operation
2. Check the outdoor temperature sensor
FAN1 ERROR
-
-
Check OLP sensor
1. Check if the service valve is open
2. Check the state of refrigerant
3. Check if connecting wire and the pipe are OK
4. Check the compressor
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM Data
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA.
FAN2 ERROR
Check Outdoor Inverter PBA
Check Outdoor Inverter PBA.
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA
Check Outdoor Inverter PBA.
-
Check the refrigerant
Check the outdoor EEPROM data and indoor option code
Check the indoor option code
-