Samsung AC TNPPEH Series User & Installation Manual page 41

Table of Contents

Advertisement

AC036/048TNPPEH (1-phase)
Indoor Unit
Cable clamp
1(L)2(N)
Indoor power
cable
AC060TNPPEH (3-phase)
Indoor Unit
Cable clamp
1(L)
2(N) L1(R)L2(S) L
Indoor power cable
Indoor power supply
Power supply
1 Φ, 220 to 240, 50 Hz
Communication cable
0.75 mm², 2 wires
DB68-09343A-00_IBIM_PAC 미라지 이집트파키스탄_IQ_EN.indd 41
1(L)
2(N)
F1
F2
Outdoor Unit
F1 F2
L N
Cable tie
Communication
Main power
cable
cable
1(L)
2(N)
F1
F1
Outdoor Unit
F1 F2
N
Cable tie
Communication
Main power
cable
cable
Max/Min(V)
Indoor power cable
±10%
0.75 mm² ↑, 3 wires
AC power: M4 screw
11
13
Tightening torque (N·m)
M3.5
M4
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for outdoor use
shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC:
H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
(Unit: mm)
Communication: M3.5 screw
9.0
7.5
0.8 to 1.2
1.2 to 1.8
41
English
2020-07-28 오전 11:08:52

Advertisement

Table of Contents
loading

Table of Contents