Project planning information

6 .11 Wiring

Electrical connection via plug-in connection terminals
(2.5 mm²) and plug-in cable glands. The latter can be
removed in order to facilitate installation. The BCU is
suitable for hard wiring only. Do not reverse phase and
neutral conductor. Different phases of a three-phase
current system must not be installed at the BCU. No
voltage may be connected to the valve and ignition out-
puts.

6 .12 BCU switched off

In general, the BCU cannot be activated when no mains
voltage is applied or the burner control unit is switched
off. The fault signalling contact is only closed when the
unit is supplied with voltage and switched on.
If the unit is switched off, an immediate program abort
with switch-off of all outputs occurs (even during the
safety time). When the unit is switched on, the program
run is restarted in standby.

6 .13 Furnace control

Switch on the system to start up the furnace, then
release the burner start via the safety interlocks and
afterwards start the burner control so that the burner
control unit may monitor the burners as intended. To
shut down the furnace, first disconnect the burner
control unit from the temperature control (burner ON
signal), then disconnect the safety interlocks and finally
switch off the system.
BCU 440 · Edition 01.17

6 .14 Mains switch

The mains switch in the unit isolates the BCU on two
poles from the mains. It does not meet the require-
ments of
EN 50156-1:2004 for a device to disconnect the
power supply.
Although the mains switch cannot be used for discon-
necting from the electrical power supply in accordance
with EN 50156, it does allow the burner to be isolated
functionally from the central control system. This func-
tion is required for manual operation.
Disconnection for electrical maintenance work is to be
implemented with an external switch per unit or group
only, in accordance with Standard EN 50156.

6 .15 Note on EC type-examination

Since EN 298 (1993) does not describe all functions of
the BCU, the operator is responsible for ensuring that
all parameters and functions are matched to the re-
spective application.