Parameters; Scanning The Parameters - Honeywell krom schroder BCU 440 Manual

Burner control unit
Table of Contents

Advertisement

Parameters

4 Parameters
Description
Burner flame signal
Program status when the most recent fault occurred
Switch-off threshold of the flame amplifier
Fault lock-out or restart
Safety time during operation t
SB
Safety time on start-up t
SA
* Adjustable using BCSoft software and a PC opto-adapter.
0 = Function inactive
1 = Function active
On parameterisation, ensure that the program se-
quence started matches the application. This param-
eter may be set in this way only if the burner can restart
as intended in all operating phases.

4 .1 Scanning the parameters

During operation, the 7-segment display shows the pro-
gram status, see page 12 (Program status and fault
messages)
The flame signal and all following parameters of the
BCU can be scanned one after the other by repeatedly
pressing the Reset/Information button (for 2 s).
In the event of a fault, the BCU halts the program run,
the display blinks and it then displays the cause of the
fault in coded form.
BCU 440 · Edition 01.17
Parameter
Value range
01
0 – 99 µA
03
x0 – x8
04
1 – 20 µA
12
0; 1
14
1; 2 s
22
3; 5; 10 s
Factory default setting
Adjustable*
1 µA
0
1 s